baltur TBG 50LX PN ME Manual De Instrucciones página 37

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

MANUAL MODE BURNER
INSTRUCTIONS
Combustion control can be carried out
over the whole modulation range whi-
le manually controlling the MPA 22
equipment. For this use modulation
connector (B) in the diagram, which is
provided with the burner as standard.
After disconnecting the 4-pole plug (A)
which takes the signals from the ther-
mostat or the RWF 40 adjustor, insert
the connector in position (B). Use the +
button to increase the gas and air sup-
ply or - to reduce it.
After the check, put the 4-pole plug (A)
back in so as to reset automatic mode
modulation.