4 Installation
NOTICE
4.2.2 Information for EMC-Compliant Installation
Requirements for cables
• Use exclusively shielded twisted-pair cables to connect the device.
• Comply with the maximum permissible connection cables length.
Shielding and equipotential bonding
• Apply the cable shield on a large contact area - ideally 360°. Use e. g. a shield terminal to this
purpose.
• Pay attention to proper cable shield fastening.
• Preferably connect the shield on both sides with low impedance to the protective earth (PE),
e.g.on the device and/or on the evaluation unit. In the event of potential differences, the
shield must only be applied on one side.
• If shielding is not possible, appropriate filtering measures must be taken.
• If the protective earth should be connected to the shield on one side only, it must be made
sure that no short-time overvoltages can appear on the signal and supply voltage lines.
4.2.3 Connecting the Connecting Wires
• Before connecting the connecting wires, check the assignment of the single wires.
• After connecting, check the proper presence of the supply voltage and the proper functioning.
If the supply voltage is reversed, the measuring system does not function.
4.2.4 Sensor Terminal Assignment
Interface
Cable, 3 m, shielded, open cable end
CAN
Signal:
Core color:
4.2.5 Electrical Installation
ATTENTION
44 - EN
No open cable wires
Connect all required cable wires / connectors before commissioning.
Insulate individually all unused ends of the output signals to avoid
short-circuits.
• Electrostatic discharges at the contacts of the connector or at the
cable ends could damage or destroy the device. Take appropriate
precautionary measures.
+V
0 V/GND
BN
WH
Device damages due to connection errors
Pay attention to the correct connection of the wires, as the device
might be damaged otherwise.
CAN_H
CAN_L
GN
YE
BA Ants LES02 - R60073.0009 - 02
Kübler Group
n.c.
n.c.
GY
PK