Ac Supply Specification; Maximum Continuous Output Current - Control Techniques UNIDRIVE SP1201 Guía Rápida

Ocultar thumbs Ver también para UNIDRIVE SP1201:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Safety
Product
Mechanical
Information
Information
Information
Field wiring connectors
Sizes 4 to 6
UL listed wire connectors are used for terminating power circuit field wiring, e.g.
Ilsco TA series

AC supply specification

The drive is suitable for use in a circuit capable of delivering not more than 100,000rms
symmetrical Amperes at 264Vac rms maximum (200V drives), 528Vac rms maximum
(400V drives) or 600Vac rms maximum (575V and 690V drives).

Maximum continuous output current

The drive models are listed as having the maximum continuous output currents (FLC)
shown in Table 11-1, Table 11-2, Table 11-3 and Table 11-4.
Table 11-1 Maximum continuous output current (200V drives)
Model
SP1201
SP1202
SP1203
SP1204
SP2201
SP2202
SP2203
Table 11-2 Maximum continuous output current (400V drives)
Model
SP1401
SP1402
SP1403
SP1404
SP1405
SP1406
SP2401
SP2402
SP2403
SP2404
Table 11-3 Maximum continuous output current (575V drives)
Model
SP3501
SP3502
SP3503
SP3504
350
Electrical
Getting
Menu 0
Information
Started
FLC (A)
5.2
6.8
9.6
11
15.5
22
28
FLC (A)
2.8
3.8
5.0
6.9
8.8
11
15.3
21
29
29
FLC (A)
5.4
6.1
8.3
11
www.controltechniques.com
Running
Advanced
Diagnostics Appendix
the motor
parameters
Model
FLC (A)
SP3201
42
SP3202
54
SP4201
68
SP4202
80
SP4203
104
SP5201
130
SP5202
154
Model
FLC (A)
SP3401
35
SP3402
43
SP3403
56
SP4401
68
SP4402
83
SP4403
104
SP5401
138
SP5402
168
SP6401
205
SP6402
236
Model
FLC (A)
SP3505
16
SP3506
22
SP3507
27
Unidrive SP Short Form Guide
UL Listing
Information
Issue Number: 2

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Unidrive sp5402

Tabla de contenido