Astralpool Elite 60 Manual De Instrucciones página 25

Sistema de electrolisis sauna
Ocultar thumbs Ver también para Elite 60:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 55
7. TROUBLESHOOTING:____________________________________________________________________________________________
Any action required to solve possible problems in the equipment should always be performed with the equipment disconnected from the
mains. Any problem not indicated in the following list should be solved by an AstralPool technician.
PROBLEM
Production indicator always indicates "0" at all production levels
The power supply is not turned on.
Free chlorine levels in the water are very low.
pH/ORP controller always show extreme values, or readings are
unstable.
Impossible calibration of the pH/ORP sensor
Slow response of the pH/ORP sensor
Check electrodes.
Verify connections between power supply and the electrolysis
cell.
Check salt concentration.
Check the system is properly connected to 230 V/50-60 Hz in the
command box of the pump.
Check th estate of teh fuse located at the bottom of the power
supply.
Check that the system produces chlorine in pool jets.
Verify that the water Chemicals parameters (pH, combined
chlorine, isocyanuric acid, etc.) are correct.
Increase filtering time.
Add chlorine stabilizer (cyanuric acid) until a concentration of 25 –
3
30 g/m
is achieved.
The cable of the pH/ORP sensor is damaged. Clean the contacts
or replace the cable.
The pH/ORP sensor has an air bubble in the membrane area.
Hold the sensor in vertical position.Shake it lightly until the bubble
moves up.
Sensor fault. The connection cable is too long or it is too near to
sources of electrical interference (motors, etc.). Replace the
sensor. Locate the unit nearer to the sensor.
Polluted or expired calibration solution.
Blocked sensor membrane. Check the membrane is not
damaged. Clean the sensor with diluted acid in water, shaking it
lightly.
Sensor fault. Replace the sensor.
Sensor electrostatically charged. During the calibration phase, the
sensors should not be dried with paper or cloth. Clean it exclusively
with water and shake it lightly.
Insufficient renovation of the analyzed water (no flow through the
sample point). Ensure that the tip of the sensor is submerged in the
water at the sample point, and that no air bubbles are present.
23
SOLUTION

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Elite 100Elite 160423534235442355

Tabla de contenido