SMA Solar Technology AG
5. Check that the four side screws sit securely in the wall
mounting bracket slots.
6. Release the inverter.

2.4 Disassembling the Inverter

Procedure:
1. Disassemble the inverter in the reverse mounting order.
2. Lift and slide the inverter out of the wall mounting
bracket slots.
3. Lift the inverter off the wall mounting bracket.

2.5 Access to the Installation Area

Danger to life from electric shock due to live DC
cables
The DC cables connected to a battery may be live.
Touching the DC conductors or the live components leads
to lethal electric shocks.
• Do not touch non-insulated cable ends.
• Do not touch any live components.
• Have the inverter and the battery mounted, installed
and commissioned only by qualified persons with the
appropriate skills.
• Observe all safety information of the battery
manufacturer.
• Always disconnect the inverter and battery from
voltage sources before performing any work on
them.
• Wait five minutes before working on the inverter.
• If an error occurs, have it rectified by qualified
persons only.
Disconnecting the inverter
Before working on the inverter, disconnect it from the utility
grid by means of the AC breaker and switch off DC using
the integrated DC load-break switch. Ensure that the
inverter cannot be unintentionally reconnected. Use a
voltage detector to ensure that the unit is disconnected
and voltage free. Wait at least five minutes after
disconnection from the utility grid and batteries before
proceeding.
Installation Manual
Observe ESD safety regulations. Discharge any
electrostatic charge by touching the grounded enclosure,
before handling any electronic component.
Procedure:
1. To open the cover, loosen the three lower front screws
using a TX 30 screwdriver. The screws are captive
screws and cannot fall out.
2. Raise the cover by 180 degrees. A magnet enables the
cover to stay open.
Figure 2.13 Loosen front screws and lift the cover
3. To close the cover, lower it into place and fasten the
three front screws.

2.6 AC Grid Connection

These instructions for AC grid connection are for qualified
personnel only. To reduce the risk of electric shock, do not
perform any maintenance work other than that specified
in the manual unless you are qualified to do so.
For fuse and RCD information, refer to Section
5, page 40. AC fuse rating must not exceed the ampacity
of the conductors used.
2  Installation
STPS60-IA-xx-12
25