10 - QUICK CONFIGURATION
This paragraph concerns a quick procedure to set the control unit
and set it at work immediately.
We recommend following these instructions, in order to
check quickly the correct operation of control unit, motor and
accessories, and then changing the configuration in case of any
non-satisfactory parameter.
1. Call up the default configuration (chapter 11).
NOTE: The DEFAULT configuration includes a photocell
connected to the FOT2 input.
m
WARNING: If you load the
installation only requires one door, set the opening time
t.AP2
to zero.
StoP
Fot1
2. Set parameters
,
to the safety devices installed on the gate
3. Check that the connection of the motors is correct:
a. Feed the unit and activate the automation with a START
order: the motors must move in opening in the correct order
b. If the direction of the movement is wrong, invert the
opening/closing motor cables that move in reverse
c. If the opening order of the doors is not correct, invert the
connections of the two motors
4. Start the self-learning cycle (chapter 12)
5. Check that the automation work properly and if necessary
modify the configuration of the desired parameters
11 - LOADING OF DEFAULT
PARAMETERS
If necessary, it is possible to restore all the parameters to their
standard or default value (see table at the end)
m
WARNING: This procedure causes the loss of all the
customized parameters.
1. Press and hold down the MENU key until the
on the display
2. Release the MENU key: the display will show
MENU key only if you want to leave this menu)
3. - If the unit controls a door, press the UP key: the display
AntE
shows
- If the unit controls another type of automation press the
DOWN key: the display shows
no
4. Press the MENU key:
will appear on the display.
Si
5. Press the DOWN key:
will appear on the display.
6. Press the MENU key: All of the parameters are returned to their
default values (chapter 16) and the display shows the control
panel
AntE
DEFAULT and the
Fot2
CoS1
CoS2
,
,
,
according
-dEF
appears
ESC
(press the
SCor
12 - SELF-LEARNING OF WORKING
TIMES
This menu allows the automatic learning of the times necessary to
open and close the gate. The encoder positions are also saved, if
enabled.
m
ATTENTION: before starting the procedure, it is
necessary to check the following points:
• Limit switches and encoder: these devices, if installed, must be
enabled through the special menu (
• ADI Interface disabled (DEFAULT): the ADI interface must be
disabled through the
• STANDARD (DEFAULT) operation mode: the
StAn
must be set on
m
WARNING: if the function PHOTOCELL SHADOW
ZONE is active, the intervention of the photocell during
the self-learning does not open the gate; the control unit
automatically sets the parametersof the shadow zone in
order to disable the photocell when the gate passes in the
position of its intervention.
Place the doors, or door, at half run and proceed with the
following points:
NOTE: if the gate has only one door, the opening time of motor 2
t.AP2
must be set at 0 (
1. Press and hold down the MENU key until the
on the display
2. Release the MENU key: the display will show
MENU key only if you want to leave this menu)
3. Press the DOWN key:
4. Press the MENU key to start the self-learning cycle for the work
cycle times.
CAUTION: This procedure varies based on the number of gate
panels and travel control devices installed (refer to the tables
outlined on the following pages).
- 44 -
FC.En
Enco
,
i.Adi
menu.
Strt
0
=
)
-APP
ESC
(press the
t.LAv
will appear on the display
).
parameter
appears