Français
Figure 6-10 Pr 05 = HUAC terminal configuration
EUR
+24V
0V
Auto
run
No
Function
06
Motor rated current
Enter the motor current rating (taken from the motor name plate).
The drive rated current is the 100% RMS output current value of the drive. This value
can be set to a lower value but not to a higher value than the drive rated current.
Pr 06 Motor rated current must be set correctly to avoid a risk of fire in the event of a
motor overload.
WARNING
No
Function
07
Motor rated speed
Enter the rated full load speed of the motor (taken from the motor name plate).
The motor rated speed is used to calculate the correct slip speed for the motor.
A value of zero entered into Pr 07 means slip compensation is disabled.
NOTE
If the full load speed of the motor is above 9999rpm, enter a value of 0 in Pr 07. This will
NOTE
disable slip compensation as values >9999 cannot be entered into this parameter.
No
Function
08
Motor rated voltage
Enter the motor rated voltage (taken from the motor name plate).
This is the voltage applied to the motor at base frequency.
If the motor is not a standard 50 or 60Hz motor, see Pr 39 on page 76 and adjust accordingly.
NOTE
No
Function
09
Motor power factor
Enter the motor rated power factor cos ϕ (taken from the motor name plate).
70
English
T1
Remote speed
T2
reference input
T3
T4
_
+
V
B1
B2
B3
H
B4
A
B5
A
B6
Hand/Off/Auto
switch
B7
Deutsch
0V
Remote current speed
reference input (A1)
+10V reference output
Not used
Analog output
(motor speed)
+24V output
Digital output
(zero speed)
Drive enable / reset
(USA: Not stop)
Run forward
(USA: Run)
Run reverse
H: Contacts made
(USA: Jog)
in 'hand' position
A: Contacts made
Not used
in 'auto' position
Range
0 to Drive rated current A
Range
0 to 9999 rpm
Range
0 to 240, 0 to 480 V
Range
0 to 1
Digidrive SK Getting Started Guide
Italiano
Español
Defaults
Drive rating
Defaults
EUR: 1500, USA: 1800
Defaults
EUR: 230 / 400
USA: 230 / 460
Defaults
0.85
Issue Number: a
Type
RW
Type
RW
Type
RW
Type
RW