Jacuzzi J-SN180F Manual De Instalación Y Funcionamiento página 11

Ocultar thumbs Ver también para J-SN180F:
Tabla de contenido

Publicidad

 
Maximum Vent Length (Indoor Models) 
1.  Determine the number of 90 degree elbows in 
the vent system.  (Two 45 degree elbows count as 
one 90 degree elbow.) 
2.  Refer to the table to find the maximum vent 
length based on the number of elbows. 
Number of 
90° Elbows 
3.Adjust switch No. 1 in the SW1 DIP switch (tan 
switches) if required by the applicable note.  
1 If the length is greater than 21   (6.4 m) then 
move switch No. 1 (SW1) to OFF. 
2 If the length is greater than 15   (4.6 m) then 
move switch No. 1 (SW1) to OFF. 
3 If the length is greater than 9   (2.7 m) then move 
switch No. 1 (SW1) to OFF. 
4 Move switch No. 1 (SW1) to OFF. 
Example:  If you have one elbow then your maximum 
vent length is 35 feet (10.7 m).  If your 
actual length is greater than 15   (4.6 m) 
then move switch no. 1 (SW1) to OFF. 
NOTICE 
If you have a longer vent length (see above), switch 
No. 1 is required to be in the  OFF posi on.  This 
ensures the water heater will run properly.  Blocked 
flue diagnos c codes and shutdowns may result if 
switch No. 1 is not in the correct posi on.  
 
Maximum vent length 
41   (12.5 m) 1 
35   (10.7 m) 2 
29   (8.8 m) 3 
23   (7.0 m) 4 
17   (5.2 m) 4 
11   (3.4 m) 4 
5   (1.5 m) 4 
Jacuzzi Signature Water Heaters J‐S180/J‐S199 
Freeze Protec on 
Make sure that in case of freezing weather that the 
water heater and its water lines are protected to 
prevent freezing.  Damage due to freezing is not 
covered by the warranty. 
Loss of freeze protec on may result in water damage 
from a burst heat exchanger or water lines.   
With electrical power supplied, the water heater will 
not freeze when the outside air temperature is as cold 
as –22°F (‐30°C) for indoor models or is as cold as –4°
F (‐20°C) for outdoor models, when protected from 
direct wind exposure.  Because of the "wind‐chill" 
effect, any wind or circula on of the air on the unit 
will reduce its ability to freeze protect. 
The unit may be drained manually.  However, it is 
highly recommended that: 
drain down solenoid valves are installed that will 
automa cally drain the unit if power is lost.   
These are available in a kit, J‐A105. 
a surge protector with terminals is installed which 
allows the solenoid valves to operate if the unit is 
disabled due to a diagnos c code.  This is 
available as J‐A106. 
In addi on, the solenoid valves should be connected 
electrically to a surge protector with terminals.  This 
allows the solenoid valves to operate if the water 
heater is disabled due to a diagnos c code.   
The freeze protec on features will not prevent the 
external piping from freezing.  It is recommended that 
hot and cold water pipes are insulated.  Pipe cover 
enclosures may be packed with insula on for added 
freeze protec on. 
In the event of a power failure at temperatures below 
freezing the water heater should be drained of all 
water to prevent freezing damage. 
 
11 

Publicidad

Tabla de contenido
loading

Tabla de contenido