Remote Annunciator
11
Specifications
11.1
Electrical
Operating voltage
Current consumption at 12 V DC
–
–
Current consumption at 24 V DC/FWR
–
–
11.1.1
Wiring Specification
Cable entries
Connections
Wire gauge
Wire type
Maximum number of annunciators per
system
Distance allowed between FACP and
annunciator
Maximum length of Option Bus wiring
11.2
Mechanics
Operating and display elements
–
–
–
–
Mounting holes back box
Housing material
Color
Dimensions (W x H x D)
–
–
Weight
Bosch Security Systems, Inc.
Standby current
Alarm current
Standby current
Alarm current
6 LEDs
LCD
Keys
Piezo
FMR-1000-RA
Back box
Installation and Operation Guide
Nominal 12 V DC or 24 V DC/FWR
25 mA maximum (only Power LED on)
150 mA maximum (with annunciator lit and piezo
on)
30 mA maximum (only Power LED on)
120 mA maximum (with annunciator lit and piezo
on)
3 knockouts for 1/2 in. diameter conduit
connectors in the back, bottom and top side
2 connectors (4 terminals)
AWG 12 to 18 (diameter 3.25 mm
Non-shielded, four conductor wire
8 (FMR-1000-RA and/or FMR-1000-RCMD)
2000 ft (610 m)
4000 ft (1219 m), depending on cable gauge and
connected devices
Fire (red), Gas Alarm (blue), Power (green),
Supervisory, Silenced and Trouble (3 x yellow)
4 line x 20 character LCD display, backlit
Acknowledge [ACK] key, 4 arrow keys
Built-in piezo sounder
2, spaced 5.5 in. (140 mm) apart
ABS-FR
Red
7.40 x 4.41 x 2.40 in. (188 x 112 x 61 mm)
7.40 x 4.41 x 1.89 in. (188 x 112 x 48 mm)
17.6 oz (500 g)
Specifications | en
15
2
2
to 0.75 mm
)
F.01U.078.097 | 3.0 | 2011.11