Lamp Test

A lamp test is accomplished by pressing and holding the acknowledge [ACK] key for more
than 3 seconds. All LEDs on the FMR-1000-RA are turned on and the LCD display is filled with
black blocks when the lamp test starts. As soon as the acknowledge [ACK] key is released, the
revision number, Option Bus address, and key lock status appear on LCD display for
3 seconds. Then the LEDs and the LCD display return to normal working mode (controlled by
the panel).
9.3

Keypad Operations

View Status
With no alarms or troubles in the system, the display message is "SYSTEM NORMAL" or
"SYSTEM NORMAL DAY" along with the current date and time.
During initialization by start-up or re-configuration, the screen indicates "System Initializing".
The panel shows the "System Resetting" screen upon reset, until the system returns to the
normal supervising condition.
If PAS or Pre-signal is turned on, the screen indicates "SYSTEM NORMAL DAY".
Any off-normal conditions are shown in groups classified as fire alarm, gas alarm, supervisory
and trouble.
Use the arrow keys to view events or conditions in the same group. Up and down keys move
the user to the previous or next event. The left and right keys switch to other groups.
NOTICE!
For system display information, refer to FPA-1000 Installation and Operation Guide
(P/N F.01U.173.607).
Acknowledge
During an alarm, pressing the acknowledge [ACK] key turns off the piezo that is sounding on
an annunciator. All the ongoing events or conditions are marked as "Acknowledged". The
24-hour trouble reminder timer starts. Any trouble event not cleared within 24 hours is sent
again and the piezo begins to beep again.
If a fire input point configured as "PAS enabled" (with global PAS enabled) is activated,
pressing the acknowledge [ACK] key within 15 seconds after a PAS activation starts the
investigation timer. This allows the user to investigate the fire alarm or take other appropriate
actions until the timer expires.
An acknowledgement operation can also be initiated by the activation of an input point
configured as an acknowledge type.
10

Troubleshooting

Display
NOT PROGRAMMED
NO COMMUNICATION
COMMUNICATION OK
F.01U.078.097 | 3.0 | 2011.11
LED
0.5 s on/0.5 s
off
0.5 s on/0.5 s
off
off
Installation and Operation Guide
Piezo
Description
0.5 s every
No communication activities on
10 s
the device address.
0.5 s every
After 60 seconds of no
10 s
communication activities on any
Option Bus address.
off
Communication on the device
address; no text received yet.