Notice; Scope Of Delivery; Device Description - Bosch FMR-1000-RA Guía De Instalación Y Operación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6
en | Notice
1

Notice

These instructions cover the installation of the Bosch FMR-1000-RA Remote Annunciator in a
fire system supervised by a Bosch FPA-1000 Analog Addressable Fire Panel or a Fire Alarm
Control Panel with similar connection conditions.
Install, test and maintain the FMR-1000-RA according to these instructions, NFPA 72, Local
Codes, and the Authority Having Jurisdiction (AHJ). Failure to follow these instructions may
result in failure of the device to operate properly. Bosch Security Systems, Inc. is not
responsible for improperly installed, tested or maintained devices.
Refer to FPA-1000 Installation and Operation Guide (P/N F.01U.173.607) for detailed wiring
style requirements and complete programming and operating instructions.
NOTICE!
NFPA 72 requires a complete system-wide functional test to be performed following any
modifications, repair, upgrades, or adjustments made to the system's components, hardware,
wiring, programming, and software or firmware.
CAUTION!
These instructions contain procedures to follow in order to avoid personal injury and damage
to equipment.
2

Scope of Delivery

Description
One Remote Annunciator (in back box with cover frame)
Tabs with different language versions for LED and key text
One hardware pack
One FMR-1000-RA Installation and Operation Guide
3

Device Description

The Remote Annunciator FMR-1000-RA is a four-wire LCD annunciator without system control
capability. It shows the LEDs and LCD display identically to the panel's and includes a piezo,
scrolling buttons and acknowledge [ACK] key. The scrolling functions and the acknowledge
[ACK] key are accessible without restriction.
The Remote Annunciator features tabs with different language versions for LED and key text.
The device allows for surface and semi-flush mounting.
Each FPA-1000 Analog Addressable Fire Panel supports up to a total of eight FMR-1000-RA
Remote Annunciators and/or FMR-1000-RCMD Remote Command Centers.