Megger BMM500 Serie Guia Del Usuario página 19

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Specification
Continuity Resistance – Ω
Limit
Min.
Indicated
Reading
0,10
0,06
0,20
0,15
0,30
0,25
0,40
0,34
0,50
0,44
0,60
0,54
0,70
0,63
0,80
0,73
0,90
0,82
1,00
0,92
SAFETY
The instruments meet the requirements for
double insulation to IEC 1010-1 (1995), EN
61010-1 (1995) to Category III*, 300V phase to
earth (ground) without the need for separately
fused test leads. If required, fused test leads are
available as an optional accessory.
16
Limit
Min.
Indicated
Reading
2,00
1,88
3,00
2,84
4,00
3,80
5,00
4,76
10,00
9,56
20,00
18,8
30,00
28,4
40,00
38,0
50,00
47,6
100,00
92,0
* Relates to the transient overvoltages likely to
be met in fixed wiring installations.
Complies with the following parts of EN61557,
Electrical safety in low voltage systems up to
1000V a.c. and 1500V d.c. – Equipment for
testing, measuring or monitoring of protective
measures:-
Part 1 –
General requirements
Part 2 –
Insulation resistance
Part 4 –
Resistance of earth
connection and equi-
potential bonding
FUSE
500mA (F) 600V, 32x 6mm Ceramic HBC 10kA
minimum.
E.M.C.
The instruments meet EN 61326-1.

Publicidad

Tabla de contenido
loading

Tabla de contenido