Flow rate max. (100% water)
Service
Accuracy up to 15 PSID =
100 kPa
Minimum ΔP for start-up
Maximum ΔP
Maximum working pressure
Close off pressure
Temperature
Connection
Leakage
Compliance
Flow rate max. (100%
water)
Service
Accuracy up to 15 PSID
= 100 kPa
Minimum ΔP for start-
up
Maximum ΔP
Maximum working pres-
sure
Close off pressure
Temperature
Connection
Leakage
Compliance
Johnson Controls declares that this product is in compliance with the essential requirements and other
relevant provisions of the PED (Pressure Equipment Directive).
Table 3: VP140 BAU 3/4" (DN20)
Water or water-glycol mixture (up to 50% glycol), quality to VDI 2035
Johnson Controls declares that this product is in compliance with the
essential requirements and other relevant provisions of the PED
(Pressure Equipment Directive).
Table 4: VP140 Cxx/Dxx
VP140CAU
9.7 GPM, 2,200 l/h
Water or water-glycol mixture (up to 50% glycol), quality to VDI 2035
3.6 psi
25 kPa
1" FNPT
VP14BAU
9.7 GPM, 2,200 l/h
± 5%
3.6 psi
25 kPa
87 psi
600 kPa
362 psi
2495 kPa
100 psi
689 kPa
14 to 248 °F
-10 to 120 °C
¾" FNPT union
ANSI Class IV IEC 60534-4
VP140CAW
11.9 GPM, 2,700 l/h
11.9 GPM, 2,700 l/h
± 5%
4.4 psi
30 kPa
87 psi
600 kPa
362 psi
2495 kPa
100 psi
689 kPa
14 to 248 °F
-10 to 120 °C
ANSI Class IV IEC 60534-4
18
VP140DAW
VP140DAY
13.2 GPM, 3,000 l/h
4.4 psi
30 kPa
1 1/4" FNPT union
P/N 14-88360-03389, Rev.C