Power requirements
Input signal
Input signal adjustments
Input impedance
Electrical connections
Mechanical connections
Protection
Output force
Mechanical stroke
Full stroke cycle time
Full stroke cycles
Audible noise rating
Fluid temperature limits
Ambient operating conditions
Ambient storage conditions
Compliance
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages
resulting from misapplication or misuse of its products.
Table 5: VA-7482-8002-RA Actuator.
24 VAC ±15% at 50/60 Hz; 24 VDC ± 15% at 2.5 at maximum power supply,
Class 2
0 to 10 VDC or 0 to 20 mA
Input Signal: 0 to 10 VDC, 2 to 10 VDC, 0 to 5 VDC, 5 to 10 VDC
100,000 ohms
18 AWG cable; 59" (1.5 m) long
M30x1.5
NEMA 2, IP43
31.4 lb (140 N) minimum)
0.25 in. (6.3mm) maximum
8 s/mm
150,000
<30 dBA
35 to 203 °F (2 to 95 °C)
32 to 122 °F (0 to 50 °C), non condensing, 90% RH
-4 to 149 °F (-20 to 65 °C), non condensing, 95% RH
United States Tested per UL2043. Suitable for Use in Other Environmental Air Space
(Plenums) in Accordance with Section 300.22 (C) of the National Electrical
Code.
UL 60730-1 Listed Type 2 Enclosure - File E194024 XAPX, XAPX7
Canada CAN/CSA E60730-1:02
Europe Johnson Controls declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive
and Low Voltage Directive
19
P/N 14-88360-03389, Rev.C