Operating Anomaly - baltur SPARKGAS 20P Manual De Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

GENERAL DIAGRAM FOR TWO-STAGE L.P.G. PRESSURE REDUC-
TION FOR BURNER OR BOILER

OPERATING ANOMALY

TYPE OF IRREGULARITY
The burner does not start.
The burner starts but the
flame does not ignite. The
burner stops consequently.
The burner starts and the
flame ignites then the bur-
nes stops.
PROBABLE CAUSE
1) Lack of currente.
2) Gas does not reach the burner.
1) The gas valves do not open.
2) There is no spark at the electrode.
3) The air pressure switch does not
give it's consent to the control box.
1) The control electrode does not de-
tect or detects the flame improperly.
7 / 6
0006080480_200710
RIMEDY
1) C heck the fuses of the feed line. Check the
fuses of the control box. Check the line of the
thermostats and the gas pressure switch.
2) C heck the opening of the detecting devices
located along the feeding pipes.
1) C heck the valves operation.
2) Check the operation of the ignition transfor-
mer. Check the position of the electrodes
ends.
3) Check the setting and operation of the air
pressure switch.
1) Check the position of the control electrode.
Check the valve of the ionisation current.
N° 8721/2/GB
Rev. 21/0/90

Publicidad

Tabla de contenido
loading

Tabla de contenido