RIB KING FAST Manual Del Usuario página 32

Operador irreversible para cancelas de batiente
Ocultar thumbs Ver también para KING FAST:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

G
B
seconds.
3 - Press and hold the PROG button for 5 seconds. The green DL2 LED will flash twice to
confirm that the stored codes have been deleted.
4 - The red programming DL1 LED remains active and you can programme new codes as
shown above if required.
5 - Reposition DIP 1 to OFF and DIP 3 to OFF.
6 - You have completed the procedure.
HOW TO CHECK IF THE MEMORY IS FULL FOR RADIO CODES USED ONLY FOR
COMPLETE OPENING
You can only check the memory if the gate is closed.
1 - Position DIP 1 to ON and then DIP 3 to ON.
2 - The green DL2 LED will flash 6 times if the memory is full (64 codes have been stored).
3 - After this, the DL1 programming LED will remain active for 10 seconds, so that you can
delete all codes if required.
4 - Reposition DIP 1 to OFF and DIP 3 to OFF.
5 - You have completed the procedure.
FUNCTIONING OF CONTROL ACCESSORIES
ATTENTION: ONLY IMPULSIVE COMMANDS HAVE TO BE CONNECTED.
Make sure that any other type of command accessories (e.g. mass detectors)
used on the installation are set in the IMPULSIVE mode, otherwise, the gate will
be operated even without the protection of the safety devices.
STEP BY STEP or AUTOMATIC commands
(K BUTT button, PED BUTT button, RADIO REMOTE button)
DIP 6 - OFF
The K BUTT, the PED BUTT button, the RADIO REMOTE buttons perform the
cyclic command open-stop-close-open-stop-etc.
DIP 6 - ON
The K BUTT, the PED BUTT button, the RADIO REMOTE buttons perform:
- the open command, if pressed with the gate completely closed
- the close command, if pressed with the gate completely opened
- no effect, if pressed during the gate opening
- the gate re-open, if pressed while the gate is closing
The K BUTT opens the gate completely, whereas the PED BUTT opens the gate partially as
described in Point F.
CLOCK FUNCTION
If you want the Clock Function must request T2 with firmware NOUP 14.
ATTENTION: A CLOCK CONNECTED TO T2 with fw 09 or more ACTIVATES THE
AUTOMATIC MOVEMENT OF THE GATE WITHOUT HAVING THE PROTECTION OF THE
SAFETY DEVICES!
The Clock Function is useful during rush hours, when traffic is heavy and the flow is slow (e.g.
entrance/exit of employees, emergencies in residential areas or car parks and, temporarily, for
removal vans) and it's necessary to keep the gate opened.
CLOCK FUNCTION APPLICATION
It is necessary to request a T2 control panel with firmware NOUP 14.
Select the automatic functioning DIP 6 ON.
It can be done by connecting a switch and/or a daily/weekly clock either in parallel to the K
BUTT button or instead of the K BUTT button. When the control board receives this command,
the gate will open and by keeping this contact closed for all the time of the gate opening, the
Clock Function is automatically activated. In fact, once reached the open position, the gate will
remain opened and all of the control board functions are blocked. Only when K BUTT contact
is released, the control board functions are re-activated and the Automatic Closing restarts (if
enabled) doing the countdown to the gate closing.
PEDESTRIAN command (PED BUTT - COM)
This command is useful to open the gate partially, just enough, for example, to permit a
pedestrian crossing. In fact, the Pedestrian command (see Point F) is carried out only by
opening the motor M1 just enough for a pedestrian to pass, as described into the Point F
procedure. From the Pedestrian opening position the Automatic Closing can be enabled or
disabled with DIP3. From the Pedestrian opening position, the gate can be completely opened
by the OPEN or by the K BUTT button or by the RADIO button.
AUTOMATIC CLOSING (from the COMPLETE open position)
The Automatic Closing from the complete open position can be enabled turning ON the DIP3.
The maximum gap of time that can be programmed is 5 minutes (see Point D and E).
AUTOMATIC CLOSING (from the PEDESTRIAN open position)
The Automatic Closing from the pedestrian open position can be enabled turning ON the DIP3.
The maximum gap of time that can be programmed is 5 minutes (see Point F).
ELECTRIC LOCK (LOCK) command 12VAC
The DIP 8 in the ON position enables the Electric Lock (MAX 15W 12V) command. The Electric
Lock (LOCK A+) will be automatically turned ON each time the gate opens. If the DIP8 is OFF,
the Electric Lock command is DISABLED. The Electric Lock remains active for 1,5 seconds.
MANUAL RELEASE FACILITY
The DIP 9 in the ON position enables the Manual Release Facility. Once the gate has
completely closed, a short reversal manoeuvre (0.2 seconds) will be done to ease manual
release.
ELECTRIC LOCK unlocking FACILITY
The DIP 9 in the ON position enables the Electric Lock unlocking Facility. From close position,
just before opening, the gate will perform a short closing manoeuvre (0.5 seconds) to ease
unlocking from electric lock.
ELECTRIC LOCK coupling FACILITY
The DIP 10 in the ON position enables the Electric Lock coupling Facility. Once the gate has
closed, a short hammering close pulse (0.5 seconds) will be done at full power to guarantee
the electric lock or mechanical bolt coupling.
FUNCTIONING OF SAFETY ACCESSORIES
PHOTOCELL (PHOT - COM)
In case the switch DIP4 is in the OFF position, the photocells are active both in gate opening
and in gate closing. In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will stop and will restart opening when the obstacle is
removed
- while the gate is still, it will not move neither in opening nor in closing.
In case of the switch DIP4 is in the ON position, the photocells are active only in gate closing.
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
- while the gate is still, it will open if a open command is request, it will remain still if a close
command is request.
The photocell input (PHOT - COM) is a NORMALLY CLOSED contact.
In case there are more couple of photocells, the contacts from all the photocell receivers must
be connected in series.
In case the photocells are not installed, this contact must be short circuited with a wire jump
(from PHOT to COM) to permit the gate to operate.
ATTENTION: In case the receiver led remains lit,
malfunctioning of the main supply is suspected.
It is advisable to connect electrically to earth the
columns or the photocells stands to the terminal A-, to
shield the photocells from external noise.
Be careful not to short circuit the system when the
supply phases are inverted!
AUTOMATIC CLOSING AFTER THE TRANSIT THROUGH THE PHOTOCELL
DIP12 ON and DIP4 OFF => If the gate is opening and a vehicle crosses the photo beam,
the gate will stop. When the vehicle leaves, the gate will close
automatically after 1 second pause.
DIP12 ON and DIP4 ON => If the gate is opening and a vehicle crosses the photo beam,
the gate will continue to open. When the vehicle leaves, the
gate will stop and then closes automatically after 1 second
pause.
DIP 12 ON and DIP 3 ON =>
(Automatic closing activated), when passing
through the gate in open position, as soon as the
beam of the photocells is cut and released, the closing
of the gate will activate immediately.
DIP 12 ON and DIP 3 OFF =>
(Automatic closing disabled), when passing
through the gate in open position, even if the beam of
the photocells is cut and released, the gate will remain
opened.
DIP 12 OFF => immediate closure after transit from the photocells disabled.
PAY ATTENTION: it is highly recommended to check photocells operation at least every 6
months.
SAFETY STRIP (EDGE - COM)
If an obstacle presses the safety strip:
- while the gate is still, it will not move neither in opening nor in closing
- while the gate is closing, the gate will open
- while the gate is opening, the gate will close.
In case the safety strip is held pressed a further quick reversion, after 2 seconds, is
performed. The gate interrupts any movement and this alarm state is indicated by 1 minute
Blinker flashing. The normal gate operations can be restored by pressing any push button or
radio commands. The safety strip input (EDGE - COM) is a NORMALLY CLOSED contact. In
case there are more than one safety strip, all their contacts must be connected in series.
In case the safety strip is not installed, this contact must be short circuited with a
wire jump (from EDGE to COM) to permit the gate to operate and the Safety Strip
test must be disabled (DIP 13 OFF).
TESTING THE SAFETY STRIP equipment
The switch DIP13 ON enables to test the safety strip equipment. The test is performed every
time the gate completes a full opening. The test is available only if the safety strip device
is equipped with a dedicated power supply input.
In fact, the safety strip equipment power supply input can be connected to the A+TEST and
A - outputs (DIP13 ON). Automatically, every time the gate completes a full opening, just
before closing, the control board switches OFF the A+TEST and A - power supply output for a
very short time. While the safety strip power supply is switched OFF, if everything is working
24Vdc
Term.
A-

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Aa14008

Tabla de contenido