POINT B - SETTINGS
DIP 1
(ON) MOTORS ROTATION DIRECTION CHECK (See Point C)
Dip 2 (ON) - setting the times (point D)
Dip 2-1 setting the pedestrian opening times (point E)
Dip 1-2 save/delete radio control codes for total opening (point F)
Dip 1-3 save/delete radio codes for pedestrian opening (point G)
Dip 1-2-3 save/delete radio codes for relay r-aux command (point H)
DIP SWITCHES CONTROL
DIP 4
Photocells always active (OFF) - Photocells active only during closing (ON)
DIP 5
Pre-blinking (ON) - Normal blinking (OFF)
DIP 6
Single pulse command (START) and RADIO - step-by-step (ON) - automatic (OFF)
DIP 7
Photocells AUTO-TEST activation (ON-activated).
DIP 8
Electric lock activation (ON-activated)
DIP 9
Electric lock pulse release (ON-activated)
DIP 10
Motors manual release facilitation (ON-activated)
DIP 11
Electric lock pulse engagement (ON-activated)
DIP 12
Selection of 1 or 2 motor operation (default OFF 2 motors)
DIP 13
Activate the radio system SUN/MOON (ON) - SUN-PRO (OFF)
DIP 14
Timed operation (OFF) - Operation with limit switches (ON)
DIP 15
Slowdown (ON - activated)
DIP 16
Contactors management (ON - activated)
DIP 17
Encoder management (ON - activated)
TYPE OF MOTOR
CODE
1
KING 230/50
AA14001
KING L 230/50
AA14010
KING 220/60
AA14002
KING L 220/60
AA14011
KING ICE 230/50
AA14019
2
MAGIC IRR. 105°
AA10960
MAGIC IRR. 180°
AA10965
MAGIC REV. 105°
AA10920
MAGIC REV. 180°
AA10930
DUKE 110°
AA10975
DUKE 180°
AA10985
PRATIC
AA18001
3
KING EVO
AA14050
KING EVO L
AA14070
KING EVO ICE
AA14060
KING EVO L ICE
AA14075
4
IDRO DUE 27/R
AA10843
IDRO DUE 27/1B
AA10844
IDRO DUE 27 SUPER/R
AA10809
IDRO DUE 27 SUPER/1B
AA10804
5
FLUID R DVI
AA10899
FLUID R SVI
AA10901
FLUID 2B DVI
AA10897
FLUID 2B SVI
AA10898
IDRO 39/R
AA10871
IDRO 39/1B
AA10876
IDRO 39/2B
AA10881
6
KING FAST 230/50
AA14008
KING 120/60
AA14003
KING L 120/60
AA14012
KING EVO 120V
AA14052
KING EVO L 120V
AA14072
7
R50
AA21580
8
IDRO C 27/1B
AA10884
IDRO C 27/2B
AA10882
IDRO C 27/R
AA10883
TORQUE TRIMMER - Electronic regulator for motor torque
Adjustment of motor torque is carried out using the TORQUE Trimmer which varies the output
voltage to the head/s of the motor/s (turn clockwise to increase torque).
DIP 18
DIP 19
DIP 20
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
25
This torque control is activated after 2 seconds form any manoeuvre begging, whereas the
motor is turned on at full power to guarantee the starting at the manoeuvre begging.
PAY ATTENTION: IF THE TORQUE TRIMMER SETTING IS CHANGED, IT IS PREFERABLE
TO REPEAT THE TIME PROGRAMMING.
LOW SPEED TRIMMER - Electronic regulator for low speed on approach
Adjustment of low speed is carried out using the LOW SPEED Trimmer which varies the
output voltage to the head/s of the motor/s (turn clockwise to increase speed). Adjustment
is carried out to establish the correct speed at the completion of opening and closing,
depending on the structure of the gate, or if there is any light friction that could compromise
the correct working of the system. The low speed is activated (DIP 15 ON) when the gate leaf
is 0.50-0.60 meters away from the complete close or open position.
ATTENTION: WHEN USING HYDRAULIC OPERATORS
When using the hydraulic operators the deceleration phase may not operate correctly;
in that case it is advisable to disable the feature of the deceleration by putting DIP
15 in the OFF mode.
TCA TRIMMER - AUTOMATIC CLOSING pause time regulator for TOTAL or PEDESTRIAN
openings
default NOT ACTIVATED and LED DL11 OFF
(trimmer fully rotated counterclockwise)
This trimmer makes it possible to adjust the pause time for total or pedestrian automatic
closing. Only with gate completely open (total) or partially open (pedestrian) and LED DL11
ON (trimmer rotated clockwise to activate the feauture).
The pause time (for a totally opened gate) can be adjusted from a minimum of 2 s up to a
maximum of 2 minutes.
The pause time (for gate open with PED. control) can be adjusted from a minimum of 2
seconds to a maximum of 30 seconds.
Ex: With TCA trimmer setted halfway, you will have 1 minute pause after the total opening
and 15 seconds of pause after the pedestrian opening prior to have the auto-close of the
gate.
R-AUX - AUXILIARY RELAY CONTACT (NO)
By default this relay is set as courtesy light (max 700 W - 3 A - 230 Vac) to operate 3 minutes
at each command, with time renewed at each command.
You can activate the R-AUX contact by TRANSMITTER by performing the memorization
procedure described in point H.
LED WARNING
DL1
PROG programming activated
DL2
M1 - gate opening
DL3
M1 - gate closing
DL4
M2 - gate opening
DL5
M2 - gate closing
DL6
STOP command (NC)
DL7
PHOTO 1 contact (NC)
DL8
PHOTO 2 contact (NC)
DL9
EDGE 1 contact (NC)
DL10 EDGE 2 contact (NC)
DL11 TCA - automatic closure time enabled
DL12 Remotes programming enabled
DL13 Card managed by APP
DL14 Opening limit switch LSO M1/ENC
DL15 Closing limit switch LSC M1
DL16 Opening limit switch LSO M2/ENC
DL17 Closing limit switch LSC M2
DL18 PROG and RADIO (on MOLEX connector) commands (green)
B.I.O
Clock command (NO)
PED.
Pedestrian command (NO)
START Single impulse command (NO)
CLOSE CLOSE command (NO)
OPEN OPEN command (NO)
C - MOTOR/S ROTATIONAL DIRECTION CONTROL
1 - Unlock the operators with the Manual Release - swing open the leaves about halfway
and lock again the operators.
2 - Turn DIP1 to ON position The red LED DL1 starts blinking.
3 - Press the PROG button and hold it - When GREEN LEDS DL2 and DL4 are on, the gate
leaves are opening (with a phase shift of 2 seconds). Check the leaves swinging and
the opening mechanical stopper position (movement is now performed in "man present"
mode, open-close-open-etc.).
If any of the leaf closes instead of opening, release PROG button, turn off the main power
G
B
(red)
(green)
(red)
(green)
(red)
(red)
(red)
(red)
(red)
(red)
(red)
(two colors)
(blue)
(red)
(red)
(red)
(red)
(green)
(green)
(green)
(green)
(green)