Note On Pipe Length; Connection Instructions -Refrigerant Piping; Cut Pipes; Remove Burrs - Airwell SDMX R32 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Note on Pipe Length

Ensure that the length of the refrigerant pipe, the number of bends, and the drop height
between the indoor and outdoor units meets the requirements shown in the following table :
The Maximum Length And Drop Height Based on Models. (Unit: m/ft.)
Type of model
North America,
Australia and the
European frequency
conversion Split
Type
Other Split Type
Bends: no more than 5 places. A minimum pipe run of 3 metres is required to minimise vibration &
excessive noise.
Connection Instructions –
Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra
care to cut and flare them properly. This will
ensure efficient operation and minimize the
need for future maintenance.
1. Measure the distance between the indoor
and outdoor units.
2. Using a pipe cutter, cut the pipe a little longer
than the measured distance.
3. Make sure that the pipe is cut at a perfect 90°
angle.
90°
Oblique Rough Warped
Page 28
Capacity (Btu/h)
Length of piping
<15K
≥15K - <24K
≥24K - <36K
≥36K - ≤60K
12K
18K-24K
30K-36K
42K-60K
Maximum drop height
25/82
30/98.4
50/164
75/246
15/49
25/82
30/98.4
50/164
DO NOT DEFORM PIPE
WHILE CUTTING
Be extra careful not to damage, dent, or
deform the pipe while cutting. This will
drastically reduce the heating e ciency
of the unit.
Step 2: Remove burrs
Burrs can a ect the air-tight seal of refrigerant
piping connection. They must be completely
removed.
Hold the pipe at a downward angle to prevent
1.
burrs from falling into the pipe.
Using a reamer or deburring tool, remove all
2.
burrs from the cut section of the pipe.
Pipe
Point down
10/32.8
20/65.6
25/82
30/98.4
8/26
15/49
20/65.6
30/98.4
Reamer