Descargar Imprimir esta página
Emerson ALCO CONTROLS Thermo TI Serie Instructions De Montage

Emerson ALCO CONTROLS Thermo TI Serie Instructions De Montage

Ocultar thumbs Ver también para ALCO CONTROLS Thermo TI Serie:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 5

Enlaces rápidos

Thermo
General information and technical data
TI series of Thermo
-Expansion Valves are
designed for refrigeration, heat pump and air
conditioning with suitable charges for the following
refrigerants:
Refrigerant
Type of valve
R22:
TI..-H...
R134a:
TI..-M...
R404A/R507
TI..-S...
R407C:
TI..-N...
R410A:
TI..-Z...
Medium temperature range TS: -45 to 70°C
Fluid group:
II
Refrigerants:
CFC, HCFC, HFC
Maximum working pressure PS: 45 bar
Factory test pressure: 49.5 bar
Hazard category:
SEP (PED 97/23/EC)
Marking: CE not allowed;
Connection DN:
Valve
Inlet
Outlet
TILE/
1/2" &
5/8"-18UNF
12mm ODF
TISE
Flare
3/4"-16UNF
TIE
Flare
Brazing adapter with copper washer for inlet (size):
TIA-M06
6 mm
TIA-014
10 mm
TIA-M10
TIA-038
Maximum bulb temperature for liquid charges:
Liquid Charge
Maximum bulb temperature
MW
100 °C
SW
85 °C
HW/NW
90 °C
ZW
60 °C
!
Safety instructions
• Read
installation
instruction
Failure to comply can result in device failure,
system damage or personal injury.
• Before opening any system make sure pressure
in system is brought to and remains at
atmospheric pressure.
• Do not use any other fluid media without prior
approval of ALCO Controls. Use of fluid not
listed could result in:
Change of hazard category of product and
consequently change of conformity assessment
requirement for product in accordance with
European
pressure
equipment
97/23/EC.
Installation
1. Valves may be installed in any direction, but
should be located as close as possible to the
distributor or evaporator inlet.
Table 1: Superheat changes (K) for one full turn of adjusting stem
Evaporating temperature °C
-45 -40 -35 -30 -25 -20 -15 -10
R 134a
7.8 6.5 5.4 4.6 3.9 3.3 2.8 2.4 2.1 1.8 1.6 1.4
R 22
4.5 3.8 3.2 2.8 2.4 2.1 1.8 1.6 1.4 1.2 1.1 1.0
R 404A
3.7 3.1 2.7 2.3 2.0 1.7 1.5 1.3 1.2 1.0 0.9 0.8
R 407C
5.1 4.2 3.5 3.0 2.5 2.2 1.9 1.6 1.4 1.2 1.1 1.0
R 507
3.6 3.0 2.6 2.2 1.9 1.7 1.4 1.3 1.1 1.0 0.9 0.8
R 410A
2.9 2.4 2.1 1.8 1.5 1.3 1.1 1.0 0.9 0.8 0.7 0.6
TI___65157__R03.doc
Installation Instructions
®
-Expansion Valve TI series
2. Be sure liquid line is connected to inlet of TI valve
after inserting orifice including strainer into the
valve (Fig 1).
3. Flare connections:
For flare joints the following subjects need to be
considered:
- Proper torque for fastening the nuts as follows:
Inlet: 40 to 50 Nm
Outlet: 50 to 60 Nm
External equalizer: 17 to 20 Nm
- Using a nut according DIN/EN/SAE/ANSI
standards.
- Shape of tube end must be in 45° angle, straight
edge, clean without swarf (Fig 3 and 4)
- Apply a few drops of refrigeration oil on surfaces
of angled tube before fastening.
Failure to do so it will not provide the proper
tightness.
Warning: If a leakage is detected at specified
torque, the flare edge and nut must be examined for
correctness. A torque over the specified value may
Ext. Equaliser
not stop the leakage. Do not over torque the nut at
1/4''& 6mm
the inlet connection. The orifice would be jammed
ODF
inside of valve and will cause an erratic function of
7/16"-20UNF
valve.
Flare
4. Brazing connections TILE (Fig 5)
TILE with stainless steel does not require any wet
rag during brazing. It is important to consider the
1/4"
following subjects:
3/8"
- Use of flux and silver rod having minimum 30%
silver
- Direct torch away from valve
5. Brazing connections TIS(E) (Fig 6):
Wrap wet rag around the valve to prevent valve
damage while brazing. Direct torch away from
valve body (max. temp. see Fig. 6).
6. Assembling of TIA Brazing adapter (Fig. 1-2):
Use supplied copper washer as shown in Fig. 1.
Make sure that the surface of brass orifice (see
arrow 1 on Fig. 1) is scratch/damage free and
thoroughly.
apply a few drops of refrigeration oil.
The proper torque for fastening the nut of adapter:
40 to 50 Nm
7. Unwind the capillary tube. Do not bend the
capillary tube at brazing joint. Allow space on top
of valve head bending (Fig. 1).
8. Securely fasten the bulb with provided strap.
Insulate bulb with suitable material against
environment (Fig. 7).
9. Be sure that the external equalizer line cannot
siphon oil from the suction line.
10. The expansion valve must be free of all
directive
contaminants. Install an ALCO Filter Drier
before the valve.
11. Check for leaks, sufficient refrigerant charge
and be sure no flash gas is present before
attempting to check valve operation.
Leakage test:
-5
0
5
10
Replacement for 02
Emerson Electric GmbH & Co. OHG
GB
Heerstr.111 – D-71332 Waiblingen
Tel.: 07151 509-0 - Fax.: -200
www.emersonclimate.eu
• After completion of installation, a test pressure
must be carried out as follows:
Proper operation of Gas charges
Warning: Valves with gas charge feature MOP
function and operate properly only if the
temperature at the bulb is below the temperature
at the head of the valve and at the capillary tube
(see Fig. 8). If valve head becomes colder than the
bulb, malfunction of the expansion valve occurs
(i.e. erratic low pressure or excessive superheat).
Superheat Adjustment (Fig. 9)
Proceed as follows if the superheat need the
readjustment:
1. Remove seal cap from side of valve.
2. Turn the adjustment screw clockwise (+) to
3. Determine superheat "SH" according to Fig. 9.
4. Replace and hand tighten seal cap.
Warning: There are max. 11 turns on the
adjustment stem (from one end to other end).
When stop is reached any further turning will
damage the valve.
See Fig. 10 for factory setting stem position:
Attention!: TILE-ZW (R410A) may require the
increase of factory static superheat setting for low
temperature refrigeration applications such as
freezers.
TI valves with standard charge for alternative
refrigerants
It is possible to use a valve with standard charge in a
system having alternative refrigerants when the
following criteria is taken into the account:
• Static
readjustment of valve
• Opening superheat changes after readjustment
valve
• Slight shifting of MOP value (if available)
The magnitude of shifting/changes is dependant on
the saturation pressure of a designed charge vs.
alternative
temperature (see table 2).
Table 2: Superheat Readjustment for alternative refrigerants
Standard Charge
alternative
(refrigerant)
refrigerant
MW (R134a)
R413A
SW/SAD (R404A)
R507
R422A
HW/HAD (R22)
R422D
Date: 20.07.2009
- According to EN378 for systems which must
comply with European pressure equipment
directive 97/23/EC
- To maximum working pressure of system for
none European installation.
increase the superheat and counterclockwise (-) to
decrease superheat. Changes in Superheat (K) per
stem turn depending on evaporating temperature
and refrigerant (see table 1). As much as 30
minutes are required for the system to stabilize
after the adjustment is made.
1. turn in (–) direction until Stop is reached
2. turn in (+) direction according to table (full
turns)
superheat
shifting
refrigerant
at
certain
Evaporating temperature
-40
-30
-20
Number of turns
1
1
-
-
/
-
/
4
3
1
3
-1
/
-1
-
/
4
4
1
1
3
+
/
+
/
+
/
2
2
4
1
3
3
+
/
+
/
+
/
2
4
4
and
therefore
evaporating
-10
0
1
3
-
/
-
/
2
4
1
1
-
/
-
/
2
2
3
3
+
/
+
/
4
4
3
3
+
/
+
/
4
4
PCN 865884

Publicidad

loading

Resumen de contenidos para Emerson ALCO CONTROLS Thermo TI Serie

  • Página 1 Emerson Electric GmbH & Co. OHG Installation Instructions Heerstr.111 – D-71332 Waiblingen ® Thermo -Expansion Valve TI series Tel.: 07151 509-0 - Fax.: -200 www.emersonclimate.eu 2. Be sure liquid line is connected to inlet of TI valve • After completion of installation, a test pressure...
  • Página 2 Emerson Electric GmbH & Co. OHG Einbauanleitung Heerstr.111 – D-71332 Waiblingen ® Thermo -Expansionsventile TI Baureihe Tel.: 07151 509-0 - Fax.: -200 www.emersonclimate.eu 3. Bördelanschlüsse: Allgemeines und Technische Daten Dichtheitsprüfung: Zur Erreichung einer optimalen Dichtigkeit Die Baureihe TI eignet sich für Kälte- und •...
  • Página 3 Emerson Electric GmbH & Co. OHG Instructions de montage Heerstr.111 – D-71332 Waiblingen Détendeur Thermostatique série TI Tel.: 07151 509-0 - Fax.: -200 www.emersonclimate.eu 3. Raccord à visser : Information générale et données techniques Test fuites : Pour les raccords à visser, les points suivants Les Détendeurs Thermostatiques série TI sont...
  • Página 4 Emerson Electric GmbH & Co. OHG Istruzioni di Installazione Heerstr.111 – D-71332 Waiblingen Valvole di Espansione Termostatiche Tel.: 07151 509-0 - Fax.: -200 Serie TI www.emersonclimate.eu 3. Attacchi flare: Informazioni generali e dati tecnici Prova di tenuta: Per attacchi a cartella, seguire le indicazioni Le valvole di espansione della serie TI sono •...
  • Página 5 Emerson Electric GmbH & Co. OHG Instrucciones de instalación Heerstr.111 – D-71332 Waiblingen Válvulas de la serie TI Tel.: 07151 509-0 - Fax.: -200 www.emersonclimate.eu Salida: 50 a 60 Nm Información general y datos técnicos Funcionamiento apropiado de las cargas de Igualación externa: 17 a 20 Nm...
  • Página 6 Emerson Electric GmbH & Co. OHG Instrukcja montażu Heerstr.111 – D-71332 Waiblingen Zawór termostatyczny rozprężny serii TI Tel.: 07151 509-0 - Fax.: -200 www.emersonclimate.eu Próba szczelności: Informacje ogólne i dane techniczne 3. Króćce śrubunkowe: • Po zakończeniu montażu należy przeprowadzić...
  • Página 7 Emerson Electric GmbH & Co. OHG Návod k montáži Heerstr.111 – D-71332 Waiblingen ® Termostatické -vstřikovací ventily TI Tel.: 07151 509-0 - Fax.: -200 www.emersonclimate.eu 3.Šroubovací připojení (pertl) Úvod a technické údaje Zkouška těsnosti: Pro dosažení co nejvyšší těsnosti spojů je nutné...
  • Página 8 Emerson Electric GmbH & Co. OHG Инструкция по эксплуатации ® Heerstr.111 – D-71332 Waiblingen Термо -расширительные вентили Tel.: 07151 509-0 - Fax.: -200 серии TI www.emersonclimate.eu Технические характеристики: с фильтром установлена во входное отверстие • После завершения работ по монтажу, ТРВ...
  • Página 9 Emerson Electric GmbH & Co. OHG Heerstr.111 – D-71332 Waiblingen TI Series Tel.: 07151 509-0 - Fax.: -200 www.emersonclimate.eu Fig. 1 Fig. 7 Fig. 8: T > T Fig. 2 T < T T = T Fig. 9 = SH (Kelvin/Rankin) = ∆ t...