6.7 - COMMAND DEVICES
Stop button (N.C. socket)
- Button to stop gate while excluding the automatic closing cycle.
For movement to resume you must press the command button or
transmitter button.
Key selector and/or partial opening button (N.O. socket)
- Opening of one gate leaf to allow pedestrian passage.
Key selector and/or commands button (N.O. socket)
- Gate closing and opening contacts, by pressing the button or
turning the selector key, the gate movement is inverted or halted
depending on which selection was just made. (see selecting
functions, dips 2 and 3).
6.8 - ELECTRICAL CONNECTION FOR THE PHOTOCELLS FUNCTIONS TEST
(DOC)
At each opening and closing command, the control board assesses the
effi ciency status of the control devices (photocells). Any anomaly found
is signalled with the fl ashing of the (PROG) LED on the control panel.
Consequently it cancels any commands coming from the remote control or
the button.
Electrical connection to enable the photocell safety test:
- the transmitter and the receiver, must be connected as per the diagram;
- set DIP switch 9 to ON to activate test operation.
IMPORTANT:
when running the safety test function, the N.C. contacts, if unused, should be excluded on the relative DIP switches (see chapter 7
"selecting functions").