Maintenance and care: Trouble shooting

Trouble shooting

Introduction
This section shows how to acknowledge and understand possible operation errors.
For a proper error search, Dantherm strongly recommends to have a remote control con-
nected and operative with the unit.
Any possible error will be displayed on:
Error signalling
Device
Unit
Handheld remote
control
Wired remote con-
trol (HCP 10/11)
PC Tool
Smartphone APP
Error displaying on a display, is a three digit information, for instance "E13" which means error
Error list
number 13.
See below list for a full description:
Number
of flashes
(wired
control)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Resetting errors
After completion of any inspection or repair, due to possible errors, the unit can be reset by
disconnecting / re-connect the 230V AC power. This will reset the controller, and the unit will
start normal operation, and also restart a new search for possible errors. This could last up to
15 minutes.
Signal
Acoustic buzzer signal from the main PCB. Connect a remote or PC
Tool, in order to get the specific error shown.
Acoustic buzzer signal as well as displaying a specific error code.
Acoustic buzzer signal and flashing LED. The number of flashes cor-
responds to an error code, followed by a 5 second break. See Error list.
Displaying error number, as well as being able to log specific opera-
tions, over a longer time span.
Displaying a specific error code.
Number
Specific error
E 1
Exhaust air fan
E 2
Supply air fan
E 3
By-pass damper
E 4
Extract air temperature sensor (T1)
E 5
Supply air temperature sensor (T2)
E 6
Extract air temperature sensor (T3)
E 7
Exhaust air temperature sensor (T4)
E 8
Room air temperature sensor (T5)
E 9
Humidity sensor, RH% (Accessory)
E 10
Outdoor temperature < -13 °C
E 11
Supply temperature < +5 °C
E 12
Fire alarm, any one of the internal sensor, is measuring a temperature
> 70 °C.
E 13
Communication error / low signal
E 14
Fire alarm, duct connected fire thermostat (Accessory)
E 15
High water level (Accessory)