1. Determine an appropriate mounting location inside the light fixture
minimizing the electric light contribution to the sensor's photocell.
Allow a minimum distance of 0.2" (5.1mm) from the wiring end of
the sensor to the wall of the fixture.
2. Drill a hole 1.30" (33.0mm) in diameter through the sheet metal in
the bottom of the fixture.
3. Add the rubber gasket to the threaded collar, and install the
sensor face down, parallel to the mounting surface. Ensure the
rubber gasket touches the inside surface of the fixture. Install
the plastic nut (or optional collar) securely against the fixture to a
torque of 25-30 in-lbs to ensure IP rating is maintained.
4. Align the locking features between the sensor and lens module
and push the lens module forward until the o-ring seals firmly.
Turn the lens module clockwise to ensure that it locks in place.
5. Connect wires as shown in the wiring diagram.
6. Restore power from the circuit breaker.
NOTE: An optional collar can be installed in place of the tightening nut.
See the Ordering Information table on page 4 for details.
Several lenses are available for use with the FSP-201. Lenses give coverage at mounting heights between 8' - 40' for applications such
as offices, warehouses, and outdoor use. Density and range of the coverage is determined by the type of lens and mounting height.
Lens modules are IP-66 rated when combined with an FSP-201 sensor mounted to an IP-66 rated outdoor fixture. See the FSP-Lx
Coverage Guide for more information.
The configuration process establishes the appropriate parameters for the FSP-201 operation. This is done through the FSIR-100
Wireless IR Configuration Tool. If no configuration steps are taken, the sensor will use its default parameter values. Use of the FSIR-100
is highly recommended for ease of troubleshooting, and especially when the FSP-201 is mounted in a high location.
The FSIR-100 is a handheld tool for changing the defaults and testing the FSP-201.It provides wireless access to the FSP-201 sensors
for parameter changes and testing. The FSIR-100 display shows menus and prompts to lead you through each process. The navigation
pad provides a simple way to navigate through the customization fields.
Within a certain mounting height of the sensor, the FSIR-100 allows modification of the system without requiring ladders or tools, simply
with a touch of a few buttons.
OUTDOORS—USE AT THE EXPOSED SENSOR COLLAR PART ONLY WHEN INSTALLED AT THE SPECIFIC LOCATION PER
Ground
Non-Dimming
Ballast
CTRL (Blue)
FSP-201
High/Low PIR Occupancy Sensor
12-32 VDC, 15mA
800.879.8585
www.legrand.us
Appliance Control
88T9
18-20 AWG Solid CU Wire Only
14-18 AWG Solid CU Wire Only
NOTE: The FSP-201 must be grounded to ensure signal integrity, not for safety ground.
INSTALLATION
USING THE FSIR-100 CONFIGURATION TOOL
INSTALLATION INSTRUCTIONS WITH A LISTED OUTDOOR ENCLOSURE.
Neutral
BZ-200 Power Pack
120 – 277 VAC (1 φ ), 50/60 Hz
20A Ballast/ELV/MLV/Tungsten/LED
LISTED
16A E-Ballast/CFL
Appliance
Control
1HP @ 120/240VAC
88T9
20A 120VAC Plug Load – Receptacle
Class 2 Output
White
Power Pack
Red
Neut.
24 VDC, 225 mA
Switch
Black
Red
Hot
Green
UL 2043 Plenum Rated
Ground
Control
Common
Any 3-Wire
24VDC
+24VDC
Sensor
www.legrand.us 800.879.8585
Class 2
16094r1
wiring only
+VDC (Red)
COM (Black)
NOTE: The Outside Fixture Wall thickness should be no
LENS OPTIONS
WIRING
Line
Ground (Green)
Lighting
Load
0-10V – (Gray)
0-10V + (Violet)
18-20 AWG Solid CU Wire Only
2
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
FSP-201
Inside Fixture
Rubber
Wall
Gasket
Outside
Fixture Wall
Tightening Nut
(or Optional Collar)
greater than 0.125" (3.18mm) for optimal sensor
mounting and security.
Ground
Dimming
Ballast/Driver
CTRL (Blue)
FSP-201
High/Low PIR Occupancy Sensor
12-32 VDC, 15mA
800.879.8585
www.legrand.us
Appliance Control
88T9
14-18 AWG Solid CU Wire Only
Rubber
Tightening Nut
Gasket
Fixture
(or Optional Collar)
Wall
Lens Assembly
Neutral
Line
BZ-200 Power Pack
120 – 277 VAC (1 φ ), 50/60 Hz
20A Ballast/ELV/MLV/Tungsten/LED
LISTED
16A E-Ballast/CFL
Appliance
Control
1HP @ 120/240VAC
88T9
20A 120VAC Plug Load – Receptacle
Class 2 Output
White
Power Pack
Red
Lighting
Neut.
24 VDC, 225 mA
Load
Switch
Black
Red
Hot
Green
UL 2043 Plenum Rated
Ground
Control
Common
Any 3-Wire
24VDC
+24VDC
Sensor
www.legrand.com • 800.879.8585