LEGRAND Wattstopper FSP-201 Instrucciones De Instalación página 3

Sensor pir para fixturas y uso exterior
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Dim-to-Off
Ballast/Driver
COM/GND (Black)
Ground (Green)
0-10V – (Gray)
0-10V + (Violet)
FSP-201
High/Low PIR Occupancy Sensor
12-32 VDC, 15mA
800.879.8585
www.legrand.us
Appliance Control
88T9
18-20 AWG Solid CU Wire Only
14-18 AWG Solid CU Wire Only
Navigate from one field to another using (up) or (down) arrow keys. The active field is
indicated by flashing (alternates) between yellow text on black background and black
text on yellow background.
Once active, use the Select button to move to a menu or function within the active
field. Value fields are used to adjust parameter settings. They are shown in "less-than/
greater-than" symbols: <value>. Once active, change them using (left) and (right)
arrow keys. The right key increments and the left key decrements a value. Selections
wrap-around if you continue to press the key beyond maximum or minimum values.
Moving away from the value field overwrites the original value. The Home button
takes you to the main menu. The Back button can be thought of as an undo function.
It takes you back one screen. Changes that were in process prior to pressing the key
are lost.
IR communication can be affected by the mounting height of the sensor and high
ambient lighting such as direct daylight or electric light such as floodlights, fluorescent
lamps, LED's and some halogen.
When trying to communicate with the FSP-201, be sure to be positioned under the
sensor without any obstructions. Every time the commissionng tool establishes
communication with the FSP-201, the controlled load will cycle.
Lights will not go to High Mode:
• Check all wire connections and verify the dimming wires are tightly secured.
• Make sure that the sensor is not obstructed.
• Check light level parameter, to find out the amount of light that the sensor is detecting. Cover the sensor lens to simulate darkness
in the room. If the lights come ON, the setpoint needs to be adjusted. If set for minimum, more than 1 fc at the sensor of ambient
light will cause the lights to be held OFF. See the new settings section for instructions.
• If lights still do not turn ON, call 800.879.8585 for technical support.
Ground
Neutral
Line
+VDC Output (Red)
Wiring with an
external DC
power supply
NAVIGATION
IR COMMUNICATION
TROUBLESHOOTING
The FSIR-100 operates on three
standard 1.5V AAA Alkaline batteries or
three rechargeable AAA NiMH batteries.
The battery status displays in the upper
right corner of the display. Three bars
next to BAT= indicates a full battery
charge. A warning appears on the
display when the battery level falls
below a minimum acceptable level. To
conserve battery power, the FSIR-100
automatically shuts off 10 minutes after
the last key press.
If communication is not successful, move closer to the sensor (if
possible).
If still not successful, there may be too much IR interference from
other sources. Programming the unit at night when there is no daylight
available may be the only way to communicate with the sensor.
3
BATTERIES
Power
BAT=
On/Off
FSP-2X1
HBP-111
Back
Left
Down
15'-32'
* Distance may vary depending on
the lighting environment
IR tx/rx
Home/Main
Menu
Up
Right/Next
Select