DIP-SWITCH SETTING
Turn off the power to the unit. This
operation should be carried out in the
installation phase, by suitably trained and
qualified personnel only.
The dip-switches are on the electronic board.
DIP
DIP 1
DIP 2
DIP 3
DIP 4
DIP 5
DIP 6
DIP 7
DIP 8
36
AGLFI10NFJ 2006_5905226_03
Position
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
Function
With shut-off valve
No shut-off valve
Water probe upstream of the valve
Water probe downstream of the valve
Continuous ventilation
Thermostat-controlled ventilation
Reduced band enabling
Normal band enabling
4-pipe fan coil
2-pipe fan coil
Supplementary heater present
Supplementary heater not present
Dead band 2°C
Dead band 5°C
Management of electric heater in replacement mode (2t + 2f )
Management of the electric heater in replacement mode