3

Installation instructions

3.1 Note on replacing the CMIX module
For the potentiometer measuring system, the
parameterised effective stroke length as well as the
minimum and maximum position are stored in the CMIX.
With this measuring system type, perform commissioning
again after replacing the CMIX; see manual on the CMIX.
If a zero point was stored, it must also be reset.
3.2 Fitting
The CMIX is mounted in an interlinking block of the CPX
terminal.
1
Screws,
Tightening torque
0.9 ... 1.1 Nm
2
CMIX
3
Interlinking block
with contact rails