3
Installation instructions
3.1 Fitting
The field bus node type CPX−FB32 is mounted on a
manifold sub−base of the CPX terminal.
1
Screws, tightening
torque 0.9...1.1 Nm
2
Field bus node
CPX−FB32
3
Manifold sub−base
with contact rails
Removing:
Remove the screws and lift the field bus node up
S
carefully.
Fitting:
1. Check the seal and sealing surfaces and refit the
sub−base.
2. Screws must be placed so that the self−cutting threads
can be used. Tighten the screws by hand in diagonally
opposite sequence. Tightening torque 0.9...1.1 Nm.
Festo CPX−FB32 0605NH English
1
2
3
19