PARAMETER SELECTION SEQUENCE
1 Shunts positioning K1, K2 and K3
- Position the shunts as follows (before modification, switch off the card) :
K3 OFF
K3 ON
2 Selection of the flow direction of the valve
2.1 Normal flow direction (by default)
- Press the OPEN button and apply the operating voltage to the card while keeping this button pressed.
G
- The green LED lights up. Release the OPEN button.
- Disconnect the card.
2.2 Inverse flow direction
- Press the CLOSE button and apply the operating voltage to the card while keeping this button pressed.
R
- The red LED lights up. Release the CLOSE button.
- Disconnect the card.
3 Selection of the type of input control signal
3.1 Voltage control signal 0-10V
- Press the MEM button and apply the operating voltage to the card while keeping this button pressed.
R
- The red LED will light up 3 times. Release this button.
- Disconnect the card.
3.2 Current control signal 0-20mA
- Press the MEM and OPEN buttons and apply the operating voltage to the card while keeping these but-
tons pressed.
R
- The red LED will light up 3 times. Release these buttons.
- Disconnect the card.
3.3 Current control signal 4-20mA (by default)
- Press the MEM and CLOSE buttons and apply the operating voltage to the card while keeping these but-
tons pressed.
R
- The red LED will light up 3 times. Release these buttons.
- Disconnect the card.
4 Learning mode
- Press the OPEN and CLOSE buttons and apply the operating voltage to the card while keeping these but-
G
R
tons pressed.
- The 2 LEDs will light up. Release these buttons and the 2 LEDs will extinguish. The card is now in the
learning mode.
R
- Press the CLOSE button to put the valve in its closed position. The red LED will light up.
- Store this selected closed position by pushing MEM + CLOSE, the red LED will light up 2 times as a
R
confirmation of acknowledgement.
- Press the OPEN button to put the valve in its open position. The green LED will light up.
G
- Store this selected open position by pushing MEM + OPEN, the green LED will light up 2 times as a
confirmation of acknowledgement.
G
- Now, the positions selected have been stored. Disconnect the card.

NORMAL OPERATING MODE

- Apply the operating voltage to the card. The green LED will light up 3 times.
- Under normal operating conditions, the green LED will light up when the drive motor opens the valve, and
G
the red LED will light up when the drive motor closes it.
- If both LEDs remain extinguished, it means that the drive motor has not been triggered.
- In the case of an over torque, the motor stops and the 2 LEDS lights then together to indicate
G
R
the action of the torque limiter. To re-start it, you must either reverse the sense of rotation, either
switch the power off and on.
DSBA3200 - Révision 29/03/2012
Input signal
Output signal
0-10V
0-10V
0-10V
0-20mA
0-10V
4-20mA
0-20mA
0-10V
0-20mA
0-20mA
0-20mA
4-20mA
4-20mA
0-10v
4-20mA
0-20mA
4-20mA
4-20mA
POSI -
PARAMETER SELECTION SEQUENCE
Schunt K1
Schunt K2
A
B
A
B
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Schunt K3
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
25/31

Publicidad

Capítulos

loading

Este manual también es adecuado para:

Er10Er20 er35Er35Er60Er100