(*) Note: When you change the operation mode of outputs EXHAUS 1, EXHAUS 2 and EXHAUS 3, you may only enter minimum ventilation outputs
before an exhauster output. For instance, before you set EXHAUS 2 as minimum ventilation, make sure the EXHAUS 1 output has been already
configured with the same setting. Similarly, outputs EXHAUS 1 and EXHAUS 2 must have been set as minimum ventilation before you set EXHAUS
3 as minimum ventilation. The same is true when you want to make these outputs operate as exhausters.
In order to set EXHAUS 2 as exhauster, make sure the EXHAUS 3 output has been previously configured with the same setting. In order to set
EXHAUS 1 as exhauster, make sure EXHAUST 2 and EXHAUS 3 are already configured as exhausters.
G01 - EXHAUS 1 Output Operation Mode
Selects EXHAUS 1 output operation mode.
- output will be set as Exhauster 1;
Exhaust
- output will be set as Minimum Ventilation 2.
Min Vent
G02 - EXHAUS 2 Output Operation Mode
Selects EXHAUS 2 output operation mode.
- output will be set as Exhauster 2;
Exhaust
- output will be set as Minimum Ventilation 3.
Min Vent
G03 - EXHAUS 3 Output Operation Mode
Selects EXHAUS 3 output operation mode.
- output will be set as Exhauster 3
Exhaust
- output will be set as Minimum Ventilation 4.
Min Vent
GXX - Temperature Differential to Turn Exhauster XX On
Temperature difference between setpoint and average temperature above which the exhauster will be activated.
GXX - Temperature Differential to Turn Exhauster XX OFF
Temperature difference to turn exhauster off.
Note 1:
EXHAUS 2 may only be set as minimum ventilation if EXHAUS 1 is already designated for this function.
Note 2:
When the differential pressure sensor is not being used by the controller to activate the curtains, the exhausters may be turned on only after
the curtains have been activated.
5.4 - Heating System
Operation parameters related to heating outputs:
Fun
Differential to Turn On Heating 1 Output
H01
Differential to Turn Off Heating 1 Output
H02
Differential to Turn On Heating 2 Output
H03
Differential to Turn Off Heating 2 Output
H04
Differential to Turn On Heating 3 Output
H05
Differential to Turn Off Heating 3 Output
H06
H01 - Differential to turn on Heating 1 Output
Determines the Heating 1 Output operating temperature. The value set for this parameter is the temperature difference between the temperature
read by the sensor and the desired control temperature, or setpoint. If the temperature is below the operating temperature, Heating 1 Output will be
activated.
H02 - Differential to turn off Heating 1 Output
Temperature difference to turn off Heating 1 output.
H03 - Differential to turn on Heating Output 2
Determines the Heating Output 2 operating temperature. The value set for this parameter is the temperature difference between the temperature
read by the sensor (*) and the setpoint. If the temperature is below the operating temperature, Heating 2 Output will be activated.
H04 - Differential to turn off Heating 2 Output
Temperature difference to turn off Heating 2 output.
H05 - Differential to turn on Heating Output 3
Determines the Heating Output 3 operating temperature. The value set for this parameter is the temperature difference between the temperature
read by the sensor (*) and the setpoint. If the temperature is below the operating temperature, Heating 3 Output will be activated.
H06 - Differential to turn off Heating 3 Output
Temperature difference to turn off Heating 3 output.
(*) The temperature that is read depends on which sensors are active. The table below shows the relation between each output and the sensor
activation.
(HEAT)
Description
Min. Max.
-50.0
0.1
-50.0
0.1
-50.0
0.1
30
CELSIUS
FAHRENHEIT
Standard
Min. Max.
Unit
Unit
50.0
°C
-30
-90
90
°F
15
°C
1.0
1
27
°F
50.0
°C
-30.0
-90
90
°F
15
°C
1.0
1
27
°F
50.0
°C
-30.0
-90
90
°F
15
°C
1.0
1
27
°F
Standard
-54
2
-54
2
-54
2