Configuration - Full Gauge V.03 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Program xx Temperature Setpoint
Configures the temperature setpoint the controller will consider for the days on which this program is running.
Temperatura pretendida del programa xx
Configura la temperatura pretendida que el controlador considerará cuando el mismo esté operando durante los días del relativo programa.

5.11 - Configuration

General operation parameters relative to the controller.
Fun
Sensor 1 Temperature Offset
C01
Sensor 2 Temperature Offset (15.1 = OFF)
C02
Sensor 3 Temperature Offset (15.1 = OFF)
C03
Humidity Sensor Offset
C04
Differential Pressure Sensor Offset (101 = OFF)
C05
Couple temperature sensor 2
C06
Couple temperature sensor 3
C07
Activation Delay
C08
LCD Contrast
C09
Protect USB Access (0-no, 1-yes)
C10
Language
C11
Temperature Units
C12
RS-485 Network Address
C13
(*) When parameters are adjusted to these values, they will be disabled.
C01 - Sensor 1 Temperature Offset
Allows compensating any deviation in temperature readings when Sensor 1 is changed.
C02 - Sensor 2 Temperature Offset
Allows compensating any deviation in temperature readings when Sensor 2 is changed. To turn Sensor 2 OFF, just select this function until "OFF" is
displayed.
C03 - Sensor 3 Temperature Offset
Allows compensating any deviation in temperature readings when Sensor 3 is changed. To turn Sensor 3 OFF, just select this function until "OFF" is
displayed.
C04 - Humidity Sensor Offset
Allows compensating any deviation in humidity readings when sensor 1 is changed.
C05 - Differential Pressure Sensor Offset
Allows compensating any deviation in differential pressure readings resulting from sensor change. To turn the sensor OFF just select this function
until "OFF" is displayed.
Important: Make sure the differential pressure sensor is installed correctly as described in 12.3.
C06- Couple temperature sensor 2
Allows the reading of temperature sensor 2 to be coupled to or uncoupled from the mean temperature calculation. For example, the sensor can be
used to control the preheating zone.
C07 - Couple temperature sensor 3
Allows the reading of temperature sensor 3 to be coupled to or uncoupled from the mean temperature calculation. For example, the sensor can be
used to control the preheating zone.
C08 - Activation Delay
Delay between the activation of the following outputs (in ascending order of priority):
- Minimum Ventilation;
- Exhausters 1-10;
- Water Sprayers 1 and 2;
- Cooling System.
The other outputs are activated independently.
C09 - LCD Contrast
LCD screen contrast.
C10 - Protect USB access
Users may choose whether to request an access code (123) when connecting a flash drive to HUMITECH SUPER.
0 - No access code;
1 - Request access code.
C11 - Language
Controller language
0 -
Portugues
1 -
English
2 -
Espanol
Description
-15.0
-15.0
-15.0
-20.0
-100
0-No
0-No
0
0
0
0
0
1
CELSIUS
FAHRENHEIT
Standard
15.0
°C
0.0
-27
27
°F
15.1
°C
15.1(*)
-27
28
°F
15.1
°C
15.1(*)
-27
28
°F
20.0
%RH
0.0
-20.0
20.0
%RH
101
Pa
101(*)
-100
101
Pa
1-Yes
-
1-Yes
0-No
1-Yes
1-Yes
-
1-Yes
0-No
1-Yes
30
sec
3
0
30
sec
10
-
5
0
10
1
-
0
1
0
2
-
0
0
2
1
-
0
0
1
247
-
1
1
247
35
Standard
0
28(*)
28(*)
0.0
101(*)
-
1-Yes
-
1-Yes
3
-
5
-
0
-
0
-
0
-
1