K1 to K21: Contactors
Note 1: Relay outputs cannot be used for direct powering the loads (except alarms).
They are designed to activate the contactor´s bobbins.
Note 2: The battery connected to terminals 25 and 26 is intended to keep the controller basic
functions operating (readings / datalogger) in case of power outage.
Note 3: In order to obtain the maximum sealing and consequent protection against humidity,
the external diameter of cables must meet the following specifications:
RS-485 SERIAL COMMUNICATION: Ø between 3.5 and 5.5 mm
TEMPERATURE AND HUMIDITY SENSOR: Ø between 5.0 and 6.2 mm
POWER AND CONTROL OUTPUTS: Ø between 7.0 and 10.2 mm
TEMPERATURE SENSORS: Ø between 3.5 and 5.5 mm
DIFFERENTIAL PRESSURE SENSORS: Ø between 3.5 and 5.5 mm

IMPORTANT

According to IEC 60364 standards:
1:
Install
protectors against overvoltage
2:
Sensor and serial communication cables can be together; however, not in the same electrical conduit through which power supply and load
driving occur.
3:
Install transient suppressors (RC filters) in parallel to loads, so as to increase the lifecycle of relays.

14 - INTEGRATING CONTROLLERS, RS-485 SERIAL INTERFACE AND COMPUTER

Distribution Box
Used to connect more than one instrument to the
Interface. Wiring must be as follows: terminal of the
instrument connects to terminal of the distribution
box, which must be connected to terminal
Interface.
Repeat the procedure for terminals and , in which
is
the cable shield (grounding is optional).
Terminal
of the distribution box must be connected
to the respective terminals on each instrument.
© Copyright 2006 • Full Gauge Controls • All rights reserved.
on power supply
A
A
A
of the
B

ENVIRONMENTAL INFORMATION

Packaging:
The materials used in the packaging of Full Gauge products are 100% recyclable.
Dispose of the packaging with specialized recycling agents.
Product:
The components used in the manufacture of Full Gauge controllers may be recycled
and reused if they are disassembled by a competent company.
Disposal:
Don't burn or dispose of controllers that reach the end of their lifecycle together with
domestic garbage. Observe applicable laws relative to product disposal. Feel free to
contact Full Gauge Controls if you have any queries.
RS-485 Network
External
Mesh
Grounded
terminal
HUMITECH SUPER
®
45
RS-485 Full
Gauge Serial
interface
RS-485 Serial Interface
Device used to connect the
Full Gauge Controls
®
instruments with Sitrad .