Pentair BERKELEY 3PL Manual De Usario página 9

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Wiring cHart – recommenDeD Wire anD fUse siZes
model
Volts
3PL
115/230
5PL
115/230
7PL
115/230
10PL
115/230
10PLS11C
115/230
15PLS11C
115/230
* Time delay fuse or circuit breakers are recommended in any motor circuit.
operation
preparing to start the pump – Deep Well
never run pump dry. Running pump without
water may cause pump to overheat, damaging seal and
possibly causing burns to persons handling pump. Fill pump
with water before starting.
never run pump against closed discharge.
To do so can boil water inside pump, causing hazardous
pressure in unit, risk of explosion and possibly scalding
persons handling pump.
1. Open the control valve as far as possible (See Figure
13). Then remove the priming plug from the pump and fill
the pump, fill all piping between the pump and the well,
and make sure that all piping in the well is full. If you
have also installed a priming tee in the suction piping,
remove the plug from the tee and fill the suction piping.
figure 13 – fill pump
figure 14 – prime pump
max. load
Branch fuse
amps
rating amps*
8.8/4.4
15/15
12.2/6.1
20/15
14.8/7.4
20/15
16.2/8.1
25/15
14.8/7.4
20/15
16.2/8.1
25/15
Open control
valve as far as
possible and
fill pump and
piping through
priming port
or priming tee.
280 0395 NF
Replace all
fill plugs and
completely
close control
valve.
556 0395 NF
Distance in feet from motor to supply
0 - 100
101 - 200
201 - 300
14/14
12/14
12/14
10/14
12/14
8/14
10/14
8/14
12/14
8/14
10/14
8/14
2. Replace all fill plugs and close the control valve
completely (See Figure 14).
3. Power on! Start the pump and watch the pressure gauge.
The pressure should build rapidly to 50 psi as the pump
primes.
4. After 2 or 3 minutes, the gauge should show pressure.
If not, stop the pump, remove the fill plugs, reopen the
control valve, and refill the pump and piping. You may
have to repeat this two or three times in order to get all
the trapped air out of the piping. Don't forget to close the
control valve each time before you start the pump.
5. When pressure has built up and stabilized at about 50
psi, slowly open the control valve (See Figure 15) and let
the pressure drop until the pressure gauge needle starts
to flutter. When the needle flutters, close the valve just
enough to stop the flutter (See Figure 15). Your pump is
now operating at its most efficient point.
A-Open Control Valve
B-Watch for Pressure Gauge to Flutter
C-Close Control Valve until Pressure
figure 15 – set control Valve
9
301 - 400
401 - 500
10/14
8/14
8/14
6/12
6/14
6/12
6/14
6/12
6/14
6/12
6/14
6/12
Stabilizes
281 0395 NF
8/12
6/12
4/10
4/10
4/10
4/10

Publicidad

Tabla de contenido
loading

Tabla de contenido