Siemens MICROMASTER 430 Serie Instrucciones De Uso página 87

Ocultar thumbs Ver también para MICROMASTER 430 Serie:
Tabla de contenido

Publicidad

Edición 05/02
Alarma
Causa
Sobrecarga motor.
A0511
Sobre-
Ciclo de carga demasiado alta.
2
temperatura I
t
Rotura de hilo del sensor de
A0512
temperatura del motor.
Pérdida de la
señal de
temperatura del
motor
Warning level of rectifier heat-sink
A0520
temperature (P) is exceeded
Rectifier Over-
Temperature
Warning level of ambient temperature
A0521
(P) is exceeded
Ambient Over-
Temperature
One phase of output is disconnected
A0523
Output fault
Identificación datos de motor (P1910)
A0541
seleccionado o funcionamiento
Identificación de
datos de motor
activo
Signal from Encoder lost
A0590
Encoder
feedback loss
warning
A0600
Aviso RTOS
Específico de la tarjeta de
A0700
comunicaciones (CB)
CB alarma 1
Específico de la tarjeta de
A0701
comunicaciones (CB)
CB alarma 2
CB Específico de la tarjeta de
A0702
comunicaciones
CB alarma 3
Específico de la tarjeta de
A0703
comunicaciones
CB alarma 4
Específico de la tarjeta de
A0704
comunicaciones
CB alarma 5
Específico de la tarjeta de
A0705
comunicaciones
CB alarma 6
MICROMASTER 430
Instrucciones de uso
6SE6400-5AE00-0EP0
6 Búsqueda de averías
Diagnosis & Eliminar
Independently of the kind of temperature determination
check:
1. P0604 motor temperature warning threshold
2. P0625 motor ambient temperature
If (P0601 = 0 or 1) Check the following:
1. Check if name plate data are correct (if not perform
quick commissioning)
2. Accurate equivalent circuit data can be found by
performing motor identification (P1910=1).
3. Check if motor weight (P0344) is reasonable.
Change if neccesary.
4. Via P0626, P0627, P0628 the standard
overtemperatures can be changed, if the motor is
nota Siemens standard motor.
If (P0601 = 2) Check the following:
1. Check if temperature shown in r0035 is reasonable.
2. Check if the sensor is a KTY84 (other sensors are
not supported)
Check the following:
1. Ambient temperature must lie within specified limits
2. Load conditions and duty cycle must be appropriate
3. Fan must turn when drive is running
Check the following:
1. Ambient temperature must lie within specified limits
2. Fan must turn when drive is running
3. fan intake air has to be without any resistance
Warning can be masked.
Stop inverter and then
1. Check encoder fitted.
2. Check connections between encoder and inverter
3. Check encoder not faulty (select P1300 = 0, run at
fixed speed, check encoder feedback signal in
P0066)
4. Increase encoder loss threshold in P492
Ver manual de usuario CB
Ver manual de la CB
Ver Manual de la CB
Ver Manual de la CB
Ver Manual de la CB
Ver Manual de la CB
87

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido