Setting is carried out in 2 phases:
- pre-adjustment without flame.
- setting the flame, to fine tune the settings
based on the combustion results.
When the burner is switched on, the
control unit displays the screen below.
• For the next step, press any button.
• The overall view of the menus is
displayed, and the air flap positions settings
menu is selected.
• Open the settings menu by pressing the
button
You must now enter the access code (see
the label on the back of the display)
• Increase or decrease the value in
increments by repeatedly pressing
• When the first figure has been set, move
the cursor to the right by pressing
• Repeat the operation until you reach the
last figure.
• Confirm the access code by pressing
The control unit then openshe settings
mode.
The screen displays the factory pre- settings
for the different positions of the air flap.
The following positions for the air flap are
presented:
• ignition position (when the menu is
opened, the curser goes to this position).
• position of the air flap during the 1st stage.
• position of the air flap when the 2nd stage
fuel oil valve is opened.
• position of the air flap during the 2nd
stage.
Modifying a settings value for the servomotor position:
- To modify the value of a position, move the cursor to the
corresponding location with the button
- Select the value to be modified using the button
value will flash.
- Increase or decrease the value in increments of 0.1° by
repeatedly pressing
or
hold the button
or
, the value will scroll quickly up or down.
- Confirm the new value using the button flashing.
N.B.:It is possible to set different positions within a large
!
range of values. However, for safety reasons, the control
unit enforces a minimum interval of 2° between the
different positions (except between the ignition position
and the 1st stage).
18
www.ecoflam-burners.com
Important
At this point, no setting position for the
servomotor has been defined, therefore
the burner cannot be started under these
conditions.
.
or
.
, the selected
. For large modifications, press and
End of settings menu without flame
or
.
.
.
When all the positions of the servomotor
have been determined according to the
required settings, it is then possible to move
on to the next section for commissioning -
"Setting the flame".
To do this, place the cursor in the lower part
of the screen on the symbol
by pressing the button
.
if it is necessary to quit the menu without
saving the pre-settings, position the cursor
on the symbol
and confirm with the
button
.
420010492200
and confirm

Publicidad