Ecoflam SmartFlam MAX P 35 AB TC TW 230-50 Manual Del Usuario página 9

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 72
Function
- TCH 2xx control box
Screen
Description
Awaiting the heat request from the boiler
Air flap is forced open for pre-ventilation.
Pre-ventilation
Closing the air flap to the ignition position,
pre-ignition
420010492200
The TCH 2xx control and safety unit
controls and monitors the forced draught
burner. The microprocessor-controlled
program sequence ensures maximum
stability of time periods, regardless of
fluctuations in the power supply voltage or
the ambient temperature. The automatic
combustion control unit is designed to
cope with brownouts. Whenever the
supply voltage drops below its rated
minimum level (< 185V), the control unit
shuts down - even in the absence of a
malfunction signal. The control unit
switches itself back on again once the
voltage has returned to normal levels (>
195V).
Locking and unlocking
The control unit can be locked (switched to
malfunction mode) by pressing the
unlocking button
and unlocked (fault
deleted), provided the unit is connected to
the mains power supply.
Always switch off the power supply
!
before installing or removing the
control unit. Do not attempt to open
or carry out repairs on the control
unit.
Screen
Pressing the
unlocking
button on the
unit for
the control unit to
... 1 second ...
he control unit to
... 2 seconds ...
the statistics to be
... 9 seconds ...
Moves the cursor upwards.
Moves the cursor downwards.
Increases the marked value.
Reduces the marked value.
Modifies/Confirms the value shown.
Unlocks the control unit.
Red LED (flashes if a fault is
present).
Description
Opening the oil valve and safety time
Flame is present, awaiting authorisation of
regulation
Burner in operation. The lower cell shows the
strength of the signal and the operating time of
the burner.
www.ecoflam-burners.com
EN
.... causes ....
unlock.
unlock.
deleted
9

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Smartflam max p 45 ab tc tw 230-400-50Smartflam max p 35 ab tl tw 230-50Smartflam max p 45 ab tl tw 230-400-50314042031404213140933 ... Mostrar todo

Tabla de contenido