• If the boiler heating request is not
present, the boiler remains on standby.
In this case, it is still possible to return to the
previous setting menu "Pre-setting without
flame". To do this, position the cursor on the
symbol
• If a boiler heating request is present
(T1- T2 contact closed), the burner starts.
The air flap is opened to move to the pre-
ventilation position.
Pre-ventilation and pre- ignition.
The air flap switches to the ignition position.
The fuel valve opens.
Awaiting flame signal.
If no flame is detected at the end of the
safety time, the control unit switches to
malfunction mode.
Flame detected.
Flame stabilisation.
The control unit awaits the regulation
authorisation.
20
www.ecoflam-burners.com
and confirm with the button
.
Setting the 1st stage.
If the flame has been detected, the control
unit sets the burner to the 1st stage as soon
as it receives the regulation authorisation.
- Adjust the fuel oil pressure for the 1st
stage depending on the required output,
using the regulator on the pump. Monitor
the combustion values continuously as you
do so (CO, CO2, soot test). If necessary,
adjust the airflow.
- To do this, modify the position of the
servomotor in 1st stage. Proceed as
described, in the paragraph "Modifying the
value of a servomotor position setting"
- Precautions: when modifying the setting
value, the servomotor will move in real time.
As a consequence, the combustion values
must be constantly checked.
Specific function: ignition checking.
If the ignition position has been modified, it
is possible to carry out a new burner start-
up to check the new ignition position,
without having to quit the settings menu. To
do this, after modifying the ignition position,
position the cursor on the symbol
initiate the new start-up using the button
Setting the opening position of the 2nd
stage fuel oil valve. After the 1st stage is
set, it is possible to set the opening value
for the 2nd stage fuel oil valve. Proceed as
described in the paragraph "Modifying the
value of a servomotor position setting".
- Precautions: in this case the servomotor
does not move immediately, but first
remains in the 1st stage position (the actual
position of the servomotor is always
displayed in the lower part of the display).
The 2nd stage valve also remains closed.
Firstly it is possible to modify the position of
the 2nd stage air flap.
Setting the 2nd stage.
To set the position of the air flap in the 2nd
stage, position the cursor on the
corresponding line on the display using the
button
. If necessary, modify the setting
value. Proceed as described in the
paragraph "Modifying the value of a
servomotor position setting".
- To make the burner actually switch to the
2nd stage, press the button
servomotor will then move the air flap to the
set position. At the same time, the 2nd
stage fuel oil valve will open, as soon as the
opening position set for the servomotor is
passed.
- Adjust the fuel oil pressure for the 2nd
stage depending on the required output,
using the regulator on the pump. Monitor
the combustion values continuously as you
do so (CO, CO2, soot test). If necessary,
adjust the airflow. To do this, modify the
position of the servomotor in the 2nd stage.
Proceed as described, in the paragraph
"Modifying the value of a servomotor
position setting"
- Precautions: when modifying the setting
value, the servomotor will move in real time.
As a consequence, the combustion values
must be constantly checked.
420010492200
, and
.
again. The