Service - Maintenance - Ecoflam SmartFlam MAX P 35 AB TC TW 230-50 Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 72
Service
- Maintenance
Burner and boiler servicing must only
be carried out by qualified personell.
The system operator is advised to take
out a service contract to guarantee
regular servicing.
Attention
• Disconnect the electrical supply before
carrying out any maintenance or
1
4
7 7
10
420010492200
cleaning work.
• The blast tube and firing head may be
hot.
Checking the exhaust gas temperature
• Check the flue gas temperature at
regular intervals.
• Clean the boiler if the flue gas
temperature is more than 30°C above
2
5
8
the value measured at the time of
commissioning.
• To simplify the check, use a flue gas
temperature indicator.
Removing the combustion head.
• See the figures in order
3
6
9
www.ecoflam-burners.com
EN
23

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Smartflam max p 45 ab tc tw 230-400-50Smartflam max p 35 ab tl tw 230-50Smartflam max p 45 ab tl tw 230-400-50314042031404213140933 ... Mostrar todo

Tabla de contenido