• Where a wall or other obstacle is in the path of the out-
door unit's intake or exhaust airflow, follow the installation
space requirements below.
• For any of the below installation patterns, the wall height
on the outlet side should be 47" or less.
• When installing under a non-moveable object, ensure 20"
or greater clearance (to allow access to internal compo-
nents).
in case of 1 unit installation
<1.5 - 3.0 ton>
Wall facing one side
More than 4"
Direction
of air
Walls facing two sides
More
than 14"
More
than 4"
More than 2"
Walls facing three sides
More than 2"
More than 14"
47" or
less
Side view
More
than 4"
More
than 14"
More than 2"
Top view
More than 4"
More than 14"
Top view
<3.5 - 5.0 ton>
Wall facing one side
More than 4"
Walls facing two sides
More than 4"
Walls facing three sides
in case of 2 units installation
More
than 40"
unit: inch
If the distance between two units is greater than 40", follow
single unit installation clearance.
4
More than 20"
Direction
of air
47" or
less
Side view
More
than 4"
More
than 20"
More
More
than 4"
than 20"
More than 4"
Top view
More than 4"
More than 20"
More than 4"
Top view
More than 4"
More than 12"
More than 40"
More than 4"
Top view
unit: inch
More than 12"
More than 8"
unit: inch