Combustion check
To limit consumption and avoid serious trouble, adjust
combustion using the appropriate instruments. It is absolutely
essential to check that the percentage of carbon monoxide (CO)
does not exceed the maximum permitted value of 0,1 % (use a
combustion analyser or other similar instrument). Please note
that our guarantee does not cover burners operating on liquid
gas (L.P.G.) in plant for which the above measures have not
been taken.
Minimum temperature
Tank 990 l.
Tank 3000 l.
Tank 5000 l.
GENERAL DIAGRAM FOR REDUCING THE LPG PRESSURE TO TWO STEPS FOR BURNER OR BOILER
Pressure gauge and pressure intake
1
step reducer
st
Output ~30 mbar
Flow rate ~ double
t h e m a x i m u m
required by the
user
2
step reducer
nd
Tank
Output ~ 30 mbar
L.P.G.
Flow rate ~ double the maximum
- 15 °C
- 10 °C
1.6 Kg/h
2.5 Kg/h
2.5 Kg/h
4.5 Kg/h
4 Kg/h
6.5 Kg/h
2nd step reducer
Output ~ 30 mbar
Flow rate ~ double the maximum required by the user
Filter (steam type)
Pressure plug
Filter (steam type)
required by the user
14 / 20
0006160076_201402
- 5 °C
- 0 °C
3.5 Kg/h
8 Kg/h
6.5 Kg/h
9 Kg/h
11.5 Kg/h
16 Kg/h
Filter
Anti-vibration joint
Ball cock
Filter
Free-standing or wall-mounted boiler
+ 5 °C
10 Kg/h
12 Kg/h
21 Kg/h
Burner