TECHNICAL FUNCTIONAL FEATURES
Operation with two progressive power stages.
Possibility of power modulation operation with installation on
modulation automatic regulator control panel (to be ordered
separately with the specific probe kit).
Combustion head with partial recycling of exhaust gases at low
NOx emissions (class II).
Easy maintenance as the mixing unit can be removed without
having to disassemble the burner from the boiler.
Gas train complete with control, operating and safety valve,
valve tightness control, minimum pressure switch, pressure
regulator and gas filter.
Flame detection by means of ionisation electrode.
Electrical system with IP40 protection rating.
Possibility to obtain optimal combustion values through
combustion air and combustion head adjustment.
Ambidextrous hinge opening for easy access to the combustion
head when burner is installed.
Valve seal control according to European Standard EN676.

BURNER CONNECTION TO THE BOILER

HEAD UNIT ASSEMNLY
The combustion head is packaged separately from the body of the
burner.
Anchor the head unit to the boiler door as follows:
Position the insulating seals on the sleeve (B).
Anchor the flange of the head unit (A) to the boiler (C) with the
stud bolts, washers and nuts provided (D).
Completely seal the gap between the burner sleeve and the
hole in the refractory material inside the boiler door with
suitable material.
ASSEMBLY OF VENTILATION SYSTEM
Position the hinge pin (E) on the burner boil aligned with the lower
half of the hinge (F), and insert it in the hole
Insert the upper half of the hinge (G) in the pin (E) and anchor it to
the sleeve with the two screws and the washer provided (H).
After aligning the holes in the head unit with the ventilating body with
the screw and lock nut (M), screw in the 4 screws with their washers
(N) to anchor the head unit onto the ventilating unit.
7 / 20