PROBLEM
THE DISPLAY SHOWS
C01
THE DISPLAY SHOWS
C05
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A30, A32, A33, A34
AND THE CPS DOES
NOT START UP
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F09, F10
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F11, F14, F15, F16, F17,
L06, L07, L08, L09, L14,
L15, L16, L17, L18, L19,
L20, L21, L22
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F03, F04, F05, A08, A09,
A10
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F42, F43, F44, L42, L43,
L44
POSSIBLE CAUSE
THE JUMPER IS MISSING
FROM THE R.E.P.O.
CONNECTOR (see "FRONT
VIEWS OF THE CPS") OR IT IS
NOT INSERTED CORRECTLY
MAINTENANCE BYPASS
ISOLATOR (SWMB)
CLOSED
THE JUMPER IS MISSING
FROM THE TERMINALS FOR
THE REMOTE MAINTENANCE
BYPASS (J2, "VIEWS OF THE
CPS CONNECTIONS")
AMBIENT TEMPERATURE
< 0°C
FAULT IN HEAT SINK
TEMPERATURE
PROBE
FAULT IN THE INPUT STAGE
OF THE CPS
PHASE 1 HAS A MUCH
LOWER VOLTAGE
THAN THE
OTHER TWO PHASES.
ANOMALOUS LOADS APPLIED
FAULT IN THE INPUT OR
OUTPUT STAGE OF THE CPS
NO CONNECTION ON ONE
OR MORE PHASES
INTERNAL PROTECTION
FUSES ON THE PHASES OR
ON THE INPUT RELAY
BROKEN
INTERNAL PROTECTION
FUSES ON THE BATTERIES
BROKEN
107
SOLUTION
Assemble the jumper or make sure that it is inserted
correctly.
Open the isolator (SWMB) located behind the door.
Insert the jumper
Heat
the
environment,
temperature to rise above 0°C and then start up the
CPS
Activate the maintenance bypass (SWMB), turn the
CPS off and back on again and exclude the
maintenance bypass. If the problem persists, contact
the nearest service centre
Activate the maintenance bypass (SWMB), turn the
CPS off and back on again and exclude the
maintenance bypass. If the problem persists, contact
the nearest service centre
Open the SWIN, switch on the CPS from the battery.
Wait for the sequence to be completed and close the
SWIN
Remove the load. Insert the maintenance bypass
(SWMB), turn the CPS off and back on again. Exclude
the maintenance bypass. If the problem persists,
contact the nearest service centre
Activate the maintenance bypass (SWMB), turn the
CPS off and back on again. Exclude the maintenance
bypass. If the problem persists, contact the nearest
service centre
Check the connections to the terminals
Contact the nearest service centre
Contact the nearest service centre
wait