OWER REDUCTION FOR
In case the output voltage is set to 200V or 208V PHASE-NEUTRAL (see the "Configuring the CPS" paragraph), the maximum
power output of the CPS is reduced compared to its nominal value, as shown in the diagram below:
C
ONFIGURING THE
Configurations which can be modified by the user from the control panel are listed in the table below.
FUNCTION
Selects mimic panel language
Language*
Output voltage
Buzzer
Operating mode**
Battery low **
Date and time**
* Press keys F1 and F4 simultaneously for t > 2 sec. and English will automatically be reset.
** Function modification can be blocked by means of the configuration software.
200/208V
CPS
DESCRIPTION
language
Selects the rated output
voltage
(Phase - Neutral)
Selects the audible alarm
operating mode
CPS operating modes
Estimated autonomy time
remaining for "battery low"
warning
CPS internal watch setup
-
PHASE
NEUTRAL LOADS
DEFAULT
• English
• Italian
English
• German
• French
• 220V
• 230V
230V
• 240V
• Normal
• Reduced: does not sound due to the
Reduced
momentary intervention of the bypass
• On line
• Eco
On line
• Emergency only
3 min.
95
POSSIBLE CONFIGURATIONS
• Spanish
• Polish
• Russian
• Chinese
1 ÷ 7 @1 min step