PROBLEM
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A13, A14, A15
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F19, F20
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A26, A27
THE DISPLAY SHOWS
THE CODE S07
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F06, F07, F08
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
L01, L10, L38, L39, L40,
L41
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A22, A23, A24, F23, L23,
L24, L25
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
L26, L27, L28
POSSIBLE CAUSE
PROTECTION DEVICE
UPSTREAM FROM THE
BYPASS LINE OPEN
BYPASS ISOLATOR OPEN
(SWBYP)
BATTERY CHARGER FAULT
BATTERY FUSES BLOWN OR
FUSE HOLDER ISOLATORS
OPEN
THE BATTERIES ARE
DISCHARGED; THE CPS
WAITS FOR THE BATTERY
VOLTAGE TO EXCEED THE
SET THRESHOLD
INPUT RELAY LOCKED
FAULT IN:
TEMPERATURE
PROBE OR CPS
COOLING SYSTEM
MAIN AUXILIARY
POWER SUPPLY
STATIC BYPASS
SWITCH
THE LOAD APPLIED TO THE
CPS IS TOO HIGH
SHORT CIRCUIT AT OUTPUT
108
SOLUTION
Restore the protection device upstream. WARNING:
check that there is no overload or short circuit at the
output of the CPS
Close the isolator located behind the door
Open the battery fuse holders (SWBATT) and insert the
maintenance bypass (SWMB), turn the CPS off
completely. Turn the CPS back on and if the problem
persists, contact the nearest service centre
Replace the fuses or close the isolators (SWBATT).
WARNING: if necessary, we recommend fuses be
replaced with others of the same type (see CPS internal
protections)
Wait for the batteries to recharge or force startup from
the "SYSTEM ON" menu
Activate the maintenance bypass (SWMB), switch off
the CPS, open the SWIN and contact the nearest
service centre.
Activate the maintenance bypass (SWMB), turn the
CPS off and back on again. Exclude the maintenance
bypass. If the problem persists, contact the nearest
service centre
Reduce the load to below the 100% threshold (or user
threshold for the code A22, A23 or A24)
Switch off the CPS.
Disconnect all the devices connected to the phase
concerned by the short circuit.
Turn the CPS back on.
Reconnect the devices one by one until the fault is
identified.