Mains Start - Up - Gtec Saturn Manual Del Usuario

Ocultar thumbs Ver también para Saturn:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

M
-
AINS START
UP
➢ Close the SWIN and SWBYP (if present) and leave the SWMB maintenance isolator open.
After a few moments the CPS will be activated. The condensers are pre-charged and the "Lock / stand-by" led will start to
flash: The CPS is in stand-by mode.
➢ Press the
confirm, press "YES" and then press the
LEDs on display will turn on for about a second and you should hear a beep. The start-up sequence ends when the CPS
enters the "load on inverter" status.
S
WITCHING OFF THE
From the main menu, select "OFF" and press
the option "YES – CONFIRM" and press
mode. With the CPS in stand-by, in order to shut down the CPS completely, open the input disconnector SWIN and bypass
disconnector SWBYP.
Note: during prolonged periods of inactivity it is advisable to shut down the CPS by opening all disconnectors. Lastly,
with the CPS off, open the battery fuse holders.
CPS
button to access the start-up menu. When requested to
89
button again to confirm. All
the submenu. Then select
. The CPS will enter "stand-by"

Publicidad

Tabla de contenido
loading

Tabla de contenido