C
ROSS SECTION OF THE CABLES
We recommend that the INPUT/OUTPUT and the BATTERY cables pass under the CPS.
As for the dimensioning of the cross section of the input and output cables, please refer to the following table:
INPUT
mains /
separate bypass (optional)
kVA
PE
L1/L2/L3
20
16
30
25
*
The cross sections shown in this table refer to a maximum length of 10 metres
** The maximum length of the cables for connection to the optional Battery Box is 3 metres
Note: the maximum cross section of the cables that can be inserted in the terminal board is:
•
50 mm
for trailing cables
2
•
70 mm
per rigid cables
2
C
ONNECTIONS
The very first connection to be carried out is that of the protection conductor (earth cable), which must
be connected to the terminal marked PE. The CPS must not operate without being connected to an
earthing system
THE INPUT AND THE BYPASS NEUTRALS MUST ALWAYS BE CONNECTED.
THE INPUT AND BYPASS LINES MUST REFER TO THE SAME NEUTRAL POTENTIAL.
Connect the input and output cables to the terminal board as shown in the figure below:
Note 1: The protection conductor (earth cable) connection must be carried out through eyelet terminal stud M6
Note 2: Connections to the BATTERY module are required only when the optional Battery Box is present
Cross section of cables (mm
N
PE
35
35
16
50
50
25
*
)
2
OUTPUT
L1/L2/L3
N
35
35
50
50
79
EXTERNAL BATTERY ** (optional)
PE
+/-
16
16
16
25
N
16
25