Internal Fan Replacement
Fan Replacement
Under normal conditions, the original fan installation will last several years. However,
the internal fan assembly is replaceable.
CAUTION: The fan circuitry is not isolated from AC mains. Turn off
power to the UPS prior to fan replacement. Fan replacement must be
performed by qualified electrical service personnel.
ATTENTION: Before removing the fan assembly, note the fan
orientation. For proper installation and connectivity, the replacement
fan must remain in its original orientation.
1
Power UPS off. Remove
the two screws that
secure the fan panel to
the UPS.
2
Remove the fan cover
and fan filter, then slide
the fan panel out and
up carefully to remove
it from the UPS, as the
internal fan power cable
is still attached to the
UPS main board.
3
Disconnect the fan cable
from the main board fan
connector.
1
2