External Battery Connections - Tripp-Lite SMART1524ET Manual Del Propietário

Ocultar thumbs Ver también para SMART1524ET:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Wiring the UPS

External Battery Connections

(Deep-Cycle Lead-Acid Batteries Only)
The UPS supports a user-supplied and assembled 24V DC (for SMART1524ET) or 48V
DC (for SMART1548ET) battery system. The batteries used must be rechargeable,
deep-cycle lead-acid type. Select batteries that meet your temperature requirements.
Connect batteries into a 24V DC (SMART1524ET) or 48V DC (SMART1548ET) UPS
system, as shown below. A battery bank of at least 100Ah, but not more than 200Ah,
is recommended. For the battery set, the recommended battery cable gauges are
6 AWG for the SMART1524ET and 8 AWG for the SMART1548ET, with a maximum
recommended length of 6.56 ft. / 2 m. The SMART1548ET requires a 48V 70A rated
fuse bank. The SMART1524ET requires a 24V 150A rated fuse bank. The battery
system attaches to the UPS via the included External Battery Connection Kit (refer to
the External Battery DC Connector Cable Assembly instruction sheet for how to wire
the external battery system to the UPS).
Battery Connection for 24V UPS System
Battery Connection for 48V UPS System
13

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Smart1548etAg-88e6Ag-88e5

Tabla de contenido