Descargar Imprimir esta página

Vortice VORT HRW 20 MONO Instrucciones Para El Instalador página 3

Ocultar thumbs Ver también para VORT HRW 20 MONO:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 6
ENGLISH
Setting operating parameters
With a suitable combination of commands you can program some of the appliance's operating parameters, as described
below:
Cycle time
The table shows:
column A: speed switch position;
column B: selected cycle time;
column C: number of LED flashes to confirm setting accepted.
Example: cycle time 50s:
• to select a cycle time 50s, set the speed
switch onto 1 and actuate the operating
mode switch, from whatever position it is
in, 3 consecutive times within a maximum
time of 2s: the cycle time will be set to 50
s. A successful setting is followed by the
LED blinking 1 time and then turning off.
Factory setting: 80s.
Number of connected units
• only for model HRW 20 RC: to select a number of units
connected to 1, 2, 4 (default):
set the speed selector on position 4 and actuate the
operating mode switch, from whatever position it is in, 3
consecutive times within a maximum time of 3s. The LED
will flash 4 times and then turn off.
• only for model HRW 20 RC: to select a number of units
connected to 3: set the speed selector on position 5 and
actuate the operating mode switch, from whatever position
it is in, 3 consecutive times within a maximum time of 3s.
The LED will flash 5 times and then turn off.
Filters reset
On both models it is necessary to reset the saturated filter status (LED on) after cleaning/replacing the filter, by taking the
following action:
set the speed selector A onto "0" /
Actuate the operating mode selector B 3 consecutive times within a maximum time of 2s. To confirm the reset, the LED
will flash 3 times and then turn off. (fig.3,4)
3 3
3x
B
1 1
3x
4 4
A
B
3x
A
1
2
3
3x
2 2
3x
A
B
C
50
1
80
2
100
3
3

Publicidad

loading

Este manual también es adecuado para:

Vort hrw 20 mono rc