Model
ACQVARIA 10-20-30
ACQVARIA 40-50-60
Ū the maximum dimensions of the opening to be made in the
suspended ceiling to house the fan coil unit are as follows:
Model
ACQVARIA 10-20-30
ACQVARIA 40-50-60
Ū do not use or store petrol or other flammable liquids near
the unit. It is very dangerous.
Ū do not install electrical equipment that is not protected with
IPX1 degree of protection (protection against vertical water
drop) underneath the unit.
Ū The manufacturer assumes no responsibility if safety and ac-
cident prevention regulations are not observed.
Note: the diffusion of air will not be as efficient if the room is
more than 3 metres high.
» Installation AQ 10-20-30
1
1
Electric box
2
Water connections
OPERATING LIMITS
Thermal carrier fluid: water
Water temperature: 5°C ÷ 70°C
Air temperature: 5°C ÷ 43°C
Supply voltage: 230 V - 50 Hz
3
UNIT DESCRIPTION
Comfort, low noise, and efficiency in perfect harmony!
The new series of hydronic cassette units ACQVARIA, with invert-
er-controlled permanent magnet BLDC motor, consists of six
models (10-20-30-40-50-60) for 2-pipe systems and four models
(10-30-40-60) for 4-pipe systems.
The engineering of the unit makes it possible to develop up to
5 kW in the cooling mode in a standard 600x600 mm modular
Distance [mm]
310
360
MAX. dimensions [mm]
690x690
820x820
2
» Installation AQ 40-50-60
1
1
Electric box
2
Water connections
Maximum water pressure during operation: 10 bar
Relative humidity limit of the ambient air:RH < 75% not
condensing
suspended ceiling and over 10 kW in the 860x860 mm modulari-
ty, with exceptionally low noise levels in the phases for maintain-
ing interior comfort.
The well-known advantages of BLDC motors are combined with
GreenTech technology (in models 10, 20, and 30), which inte-
grates the inverter directly into the fan drive assembly.
ACQVARIA leverages the entire Galletti, MYCOMFORT, EVO , and
2
25
WC66000401