Delay
• Rise Time (Off to On) determines the delay of the signal flow from the moment the sensor
becomes covered until the Primary Value is set.
• Fall Time (On to Off) determines the delay of the signal flow from the moment the sensor
becomes uncovered until the Primary Value is reset.
The delay timers have a range of values from 0.0 to 100.0 seconds.
• Go to Input > Transducer Block: Discrete Input > Delay > Rise Time (Off to On) and set the
value from 0 to 100 seconds.
• Go to Fall Time (On to Off), and set the value from 0 to 100 seconds.
If the sensor status changes before the delay interval is complete, the timer is reset to
Note:
its initial value and restarted.
Inversion
When Inversion Output = On, the level status undergoes a logical inversion.
• Go to Output > Function Block: Discrete Input > Inversion Output > Off or On
Failsafe Mode
Go to Output > Function Block: Discrete Input > Fail Safe Mode > Fail Safe Mode and select
one of the three options:.
Failsafe Mode
The default value is used as the output
value.
Store the last valid output value.
The calculated output value is incorrect.
Resetting
Open the Device Menu Master Reset and select one of the three options:
Factory Reset (restart/cold startup)
Recreates the delivery status. It resets most parameters to the factory setting.
Warm start (new start-up)
Disconnects then restarts Pointek CLS200/300. Communication is interrupted and re-
established. Use it if, for example, the PROFIBUS address has been changed.
Resetting the PROFIBUS address to 126
Please see the full manual for details.
7ML19985XA82
Pointek CLS200/300 (Digital) – QUICK START MANUAL
All manuals and user guides at all-guides.com
The predefined preset safety value is output (status code
U_075).
The last valid output value is output (status code U_071).
The bad output value is accompanied by the status which