High Condenser Temperature Alarm Management - Carel ir33+FMC Guía Rápida

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3.16 High condenser temperature alarm management

The condenser temperature can be monitored and high temperature situations signalled, most likely when
the condenser is blocked. The following diagram describes the alarm.
A probe has to be configured as a condenser probe ( see /A2;3;4).
If a cht pre alarm is activated, the controller forces the Fullmotion compressor to the min. speed cmf.
If a CHt alarm is activated, the Fullmotion compressor is forced OFF.
See the standard user manual for details on how to reset the alarm.
Cod.
Parameter
Ac
High condenser temperature alarm threshold
AE
High condenser temperature alarm differential
High condenser temperature alarm delay
Acd
0 = Immediate alarm
Alarms involved
Cod.
Message
cht
High cond. temperature pre-alarm
CHt
High condensing temperature alarm
Ac
Sc Ac - AE/2
Ac - AE
ON
cht
OFF
ON
CHT
OFF
Fig. 3.h
17
t
t
t
Acd
UOM
Dis.
Type
°C/°F
C
A
°C/°F
C
A
Min
C
I
ir33+ wide Fullmotion - +040000055 - rel. 1.0 - 09.06.2014
ENG
Def.
Max
Min
70
200
0
10
20
0,1
0
250
0
Tab. 3.n

Publicidad

Tabla de contenido
loading

Tabla de contenido